Indoor Fan Motor Control - Toshiba RAS-B16N3KV2-E1 Service Manual

Indoor unit/outdoor unit
Hide thumbs Also See for RAS-B16N3KV2-E1:
Table of Contents

Advertisement

Item
2. Indoor fan
<In cooling operation>
motor control
(This operation controls the fan speed at indoor unit side.)
The indoor fan (cross flow fan) is operated by the phase-
control induction motor. The fan rotates in 5 stages in
MANUAL mode, and in 5 stages in AUTO mode, respec-
tively. (Table 1)
COOL ON
Fan speed setup
AUTO
Ta
[ ˚C ]
+2.5
a
+2.0
b
+1.5
c
+1.0
d
+0.5
e
Tsc
Mode
Fan speed
level
Cool
Heat
WF
UH
WE
UH
WD
H
M+
WC
M+
WB
M
WA
M
W9
L+
W8
L+
W7
L
L-
W6
L-
W5
UL
UL
W4
W3
SUL
W2
SUL
W1
Mode
Fan speed
level
Cool
Heat
WF
UH
WE
UH
WD
H
M+
WC
M+
WB
M
WA
M
W9
L+
W8
L+
W7
L
L-
W6
L-
W5
UL
UL
W4
W3
SUL
W2
SUL
W1
Operation flow and applicable data, etc.
MANUAL
Indication
L
L+
M
M+
H
Air volume AUTO
M+(WB)
*3
*3 : Fan speed = (M + –L) x 3/4 + L
*4
*4 : Fan speed = (M + –L) x 2/4 + L
*5
*5 : Fan speed = (M + –L) x 1/4 + L
(Linear approximation
L(W6)
from M+ and L)
(Table 1) Indoor fan air flow rate
RAS-B10N3KV2-E1
Cooling
Fan speed Air flow rate
Dry
(rpm)
(m3/h)
1120
515
H
1120
515
UH
1120
515
H
1040
465
M+
1000
440
M
960
415
900
378
L
L+
860
353
780
303
L
650
222
L-
620
203
UL
600
191
SUL/SL-
580
179
540
154
500
129
RAS-B16N3KV2-E1
Cooling
Fan speed Air flow rate
Dry
(rpm)
(m3/h)
1510
758
H
1480
730
UH
1430
708
H
1280
615
M+
1280
615
M
1150
534
1100
502
L
L+
980
428
920
390
L
900
378
L-
840
340
UL
840
340
SUL/SL-
770
297
620
203
520
141
(Fig. 1)
Fan speed
W6
(L + M) / 2
W9
(M + H) / 2
WC
(Fig. 2)
Heating
Fan speed Air flow rate
Fan speed Air flow rate
(rpm)
(m3/h)
(rpm)
1200
565
1300
1200
565
1300
1100
502
1200
1000
440
1090
1000
440
1080
870
359
980
870
359
980
750
284
880
700
253
770
650
222
770
650
222
720
520
141
690
520
141
670
520
141
520
500
129
500
Heating
Fan speed Air flow rate
(rpm)
(m3/h)
1510
758
1510
758
1480
730
1430
708
1280
615
1220
577
1150
534
1000
440
980
428
920
390
900
378
840
340
770
297
620
203
520
141
– 32 –
FILE NO. SVM-15006
Description
* Symbols
UH
: Ultra High
H
: High
M+
: Medium+
M
: Medium
L+
: Low+
L
: Low
L-
: Low–
UL
: Ultra Low
SUL
: Super Ultra Low
* The fan speed broadly varies due
to position of the louver, etc.
The described value indicates one
under condition of inclining
downward blowing.
1) When setting the fan speed to L,
L+, M, M+ or H on the remote
controller, the operation is
performed with the constant
speed shown in Fig. 1.
2) When setting the fan speed to
AUTO on the remote controller,
revolution of the fan motor is
controlled to the fan speed level
shown in Fig. 2 and Table 1
according to the setup tempera-
ture, room temperature, and heat
exchanger temperature.
RAS-B13N3KV2-E1
Cooling
Heating
Fan speed Air flow rate
(m3/h)
(rpm)
(m3/h)
627
1300
627
627
1300
627
565
1190
558
496
1080
490
490
1080
490
428
980
428
428
980
428
365
870
359
297
770
297
297
770
297
266
720
266
247
690
247
235
670
235
141
520
141
129
500
129