Electrical Data - 2 Comp High Efficiency - York YCIV Manual

Air-cooled screw liquid chillers with variable speed drive
Table of Contents

Advertisement

Electrical Data - 2 Comp High Efficiency

MODEL NO./NAMEPLATE
INPUT
INPUT
YCIV E/V
VOLTS (9)
FREQ
400
50
0590
400
50
0630
400
50
0700
400
50
0760
400
50
0800
400
50
0830
400
50
0930
CONTROL
YCIV E/V
KVA (7)
1.8
0590
1.8
0630
1.8
0700
1.8
0760
1.8
0800
1.8
0830
0930
1.8
See page 64 for Electrical Data footnotes.
58
HIGH EFFICIENCY YCIV_ _ _ _ E/V
STD. & ULTRA QUIET COND.
FANS
COMPRES-
CONDENSER FANS
SOR
RLA (5)
QTY.
FLA (EA)
132
4
3.1
134
5
3.1
185
5
3.1
170
5
3.1
170
6
3.1
180
6
3.1
233
6
3.1
UNIT SHORT CIRCUIT WITH-
STAND (KA)
CIRCUIT
TERMINAL
BREAKER
BLOCK (STD)
(OPT)
30KA
65KA
30KA
65KA
30KA
65KA
30KA
65KA
30KA
65KA
30KA
65KA
30KA
65KA
SYSTEM 1
HIGH HEAD/STATIC COND. FANS
COMPRES-
CONDENSER FANS
SOR
RLA (5)
QTY.
FLA (EA)
132
4
9.3
134
5
9.3
185
5
9.3
170
5
9.3
170
6
9.3
180
6
9.3
233
6
9.3
FIELD WIRING & PROTECTION
STD. & ULTRA QUIET COND. FANS
RECOMMENDED
MINIMUM CKT.
FUSE/CKT.
AMPACITY
BREAKER
(MCA) (3)
RATING (4)
322
400
344
400
388
450
412
500
433
500
443
500
506
600
FORM 201.23-EG2 (713)
TWO-SPEED COND. FANS
COMPRES-
CONDENSER FANS
SOR
RLA (5)
QTY.
FLA (EA)
138
4
3.8
139
5
3.8
196
5
3.8
180
5
3.8
178
6
3.8
189
6
3.8
246
6
3.8
MAX. INVERSE
MAX DUAL
TIME CKT.
ELEMENT FUSE
BRKR. RATING
SIZE (2)
(2)
450
450
450
450
500
500
500
500
600
600
600
600
700
700
JOHNSON CONTROLS