Electrical Data - 2 Comp High Efficiency - York YCIV0177S/P Manual

Air-cooled screw liquid chillers with variable speed drive, style a
Table of Contents

Advertisement

Electrical Data - 2 Comp High Efficiency

MODEL NO./NAMEPLATE
INPUT
INPUT
YCIV E/V
VOLTS (9)
FREQ
460
60
0157
380
60
460
60
0177
380
60
460
60
0187
380
60
460
60
0197
380
60
460
60
0207
380
60
460
60
0227
380
60
460
60
0247
380
60
CONTROL
YCIV E/V
KVA (7)
1.8
0157
1.8
1.8
0177
1.8
1.8
0187
1.8
1.8
0197
1.8
1.8
0207
1.8
1.8
0227
1.8
1.8
0247
1.8
92
HIGH EFFICIENCY YCIV_ _ _ _ E/V
STD. & ULTRA QUIET COND.
FANS
COMPRES-
CONDENSER FANS
SOR
RLA (5)
QTY.
FLA (EA)
110
4
2.8
139
4
3.5
111
5
2.8
141
5
3.5
154
5
2.8
195
5
3.5
141
5
2.8
179
5
3.5
141
6
2.8
179
6
3.5
150
6
2.8
190
6
3.5
194
6
2.8
245
6
3.5
UNIT SHORT CIRCUIT
WITHSTAND (KA)
TERMINAL
CIRCUIT
BLOCK (STD)
BREAKER (OPT)
30KA
65KA
30KA
65KA
30KA
65KA
30KA
65KA
30KA
65KA
30KA
65KA
30KA
65KA
30KA
65KA
30KA
65KA
30KA
65KA
30KA
65KA
30KA
65KA
30KA
65KA
30KA
65KA
SYSTEM 1
HIGH HEAD/STATIC COND. FANS
COMPRES-
CONDENSER FANS
SOR
RLA (5)
QTY.
FLA (EA)
139
4
9.3
141
5
9.3
195
5
9.3
179
5
9.3
179
6
9.3
190
6
9.3
245
6
9.3
FIELD WIRING & PROTECTION
STD. & ULTRA QUIET COND. FANS
RECOMMENDED
MINIMUM CKT.
FUSE/CKT.
AMPACITY
BREAKER RAT-
(MCA) (3)
ING (4)
270
300
341
400
288
350
365
450
325
400
411
500
345
400
437
500
362
450
458
600
371
450
469
600
424
500
536
700
FORM 201.23-EG1 (1013)
TWO-SPEED COND. FANS
COMPRES-
CONDENSER FANS
SOR
RLA (5)
QTY.
FLA (EA)
MAX. INVERSE
MAX DUAL
TIME CKT.
ELEMENT FUSE
BRKR. RATING
SIZE (2)
(2)
350
350
450
450
400
400
500
500
450
450
600
600
450
450
600
600
500
500
600
600
500
500
600
600
600
600
700
700
JOHNSON CONTROLS

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents