box 105
Set multimeter to "measure resistance".
Measure the resistance of the safety sensor.
We reserve the right to make technical modifications
48
Servicing manual Gas condensing boiler Buderus 500-24/S, 500-24/C and 500-28/C • Issued 02/2006
Pull out the plug of the flow NTC sensor.
box 108
Set multimeter to "measure resistance".
Measure the resistance of the flow NTC sensor.
box 109
Measure the electrical resistance of the flow NTC sensor
and safety sensor.
Measure the electrical resistance of the flow NTC sensor
and check the earth (ground) connection of the safety
sensor. This must be infinitely high.
The measured resistance of the flow NTC sensor is
virtually identical to that of the safety sensor.