External Sw - Panasonic WH-UD09HE5-1 Operating Instructions Manual

Air-to-water hydromodule + tank
Hide thumbs Also See for WH-UD09HE5-1:
Table of Contents

Advertisement

Menus
For installer
Menu

External SW

5.9
16
Default Setting
Setting Options / Display
Control pattern Advanced parallel Heat Yes
• Buffer Tank is activated only after selecting
"Yes".
Set the temperature
-8 °C
threshold to start the
bivalent heat source.
Delay timer to start
the bivalent heat
0:30
source
(in hour and minutes).
Set the temperature
-2 °C
threshold to stop the
bivalent heat source.
Delay timer to stop
the bivalent heat
0:30
source
(in hour and minutes).
Control pattern Advanced parallel DHW Yes
• DHW Tank is activated only after selecting
"Yes".
Delay timer to start
the bivalent heat
0:30
source
(in hour and minutes).
No