Electrical Requirements - Brant Radiant Heaters AG2-20-65 Manual

Gas-fired infrared agricultural tube heater ag2 series
Table of Contents

Advertisement

AG2
Series
Wiring
Electric Shock
Field wiring to the tube heater must be connected and grounded according to the guidelines
in the Tube Heater General Manual and Series Insert Manual and in accordance with
national, state, provincial and local codes. In the United States refer to the most current
revisions to the ANSI/NFPA 70 Standard and in Canada refer to the most current revisions
to the CSA C22.1 Part I Standard.
Figure 3.34
Field Wiring Diagrams
A. Single Heater, Single Thermostat. No Relay Board (white label)
NOTE: If optional yellow
control cord is installed,
the following colors apply:
24VAC: Green
Low: White
High: Black
N
Low
High
24VAC
THERMOSTAT
B. Multiple Heaters, Single Thermostat. With a Relay Board (HLRB orange label)
WARNING
!
1/4" spade
terminals required
(as supplied)
24V
1
2
LO HI
Additional wire needed on thermostats
requiring constant power.
3.0
Installation
Ground Screw
on Control Box
BURNER BOX
43

Electrical Requirements

PANEL GROUND
NOTE: If optional black
power cord is installed,
then L1 is brown or
black and Neutral is blue
or white.
L1
N
120 Volt Power
(observe polarity)
Wiring

Advertisement

Table of Contents
loading

Table of Contents