GE AF-650 GP Quick Installation Manual page 36

Opcmbtcp modbus tcp option enclosed drive panel
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

O-10 Control Word Profile
Select the interpretation of the control and status words corresponding to the installed network. Only the selections valid for the network installed in slot A will
be visible in the Keypad display.
For guidelines in selection of GE Drive profile [0] please refer to the Serial communication via RS 485 Interface section.
Option:
[0] *
Drive Profile
O-13 Configurable Status Word STW
Option:
[0]
No function
[1] *
Profile Default
[2]
Alarm 68 Only
[3]
Trip excl Alarm 68
[16]
T37 DI status
O-14 Configurable Control Word CTW
Option:
[0]
None
[1] *
Profile default
[2]
CTW Valid, active low
O-50 Coasting Select
Option:
[0]
Digit Input
[1]
Bus
[2]
Logic AND
[3] *
Logic OR
NB!
This parameter is active only when par. O-01 Control Site is set to [0] Digital and control word.
O-51 Quick Stop Select
Select control of the Quick Stop function via the terminals (digital input) and/or via the network.
Option:
[0]
Digital Input
[1]
Bus
[2]
Logic AND
[3] *
Logic OR
NB!
This parameter is active only when par. O-01 Control Site is set to [0] Digital and control word.
Function:
Function:
This parameter enables configuration of bits 12 – 15 in the status word.
Function corresponds to the profile default selected in par. O-10 Control Word Profile.
Only set in case of an Alarm 68.
Set in case of a trip, except if the trip is executed by an Alarm 68.
The bit indicates the status of terminal 37.
"1" indicates T37 is high (normal)
only available in AF-650 GP.
Function:
Selection of control word bit 10 if it is active low or active high
Function:
Select control of the coasting function via the terminals (digital input) and/or via the network.
Activates command via a digital input.
Activates command via the serial communication port or network option module.
Activates command via the network/serial communication port, AND additionally via one of the digital
inputs.
Activates command via the network/serial communication port OR via one of the digital inputs.
Function:
Modbus TCP
6
35