Page 1
NOVO HIGH EFFICIENCY GAS FIRE MODELS : P23G, L23G INSTALLATION AND USER INSTRUCTIONS All instructions must be handed to user for safekeeping Revision D - 11/09 Country(s) of destination - GB/IE W J Court & Sons Limited • Stourvale Road • Lye • Stourbridge • West Midlands • DY9 8PP Tel: +44 1384 893060 •...
Page 2
P23 Novo graphite P23 Novo passion flower L23 Novo chrome P23 Novo maple leaf...
INSTALLATION INSTRUCTIONS Preliminary Notes Before Installation This appliance is a high efficiency, flueless, flame effect gas fire. It provides radiant and con- vected warmth both efficiently and safely utilising the latest type catalytic convertor burner technology. The appliance incorporates a combustion monitoring system (Oxygen Depletion System). It must not be adjusted or put out of operation.
APPLIANCE DATA Model L23 Novo P23 Novo L23 Novo LPG P23 Novo LPG Gas Group Gas Category Inlet Pressure (±2.0mbar) 20 mbar 20 mbar 37 mbar 37 mbar Max Energy Input (Gross) 2.0 kW 2.0 kW 1.7 kW 1.7 kW (Net) 1.8 kW 1.8 kW...
SITE REQUIREMENTS (continued) Clearances to non-combustibles Non combustible surfaces are defined as brick, metal, marble, concrete etc. and also a number of man-made materials impervious to flame. If in doubt refer to the material manufacturer for further information before pro- ceeding with installation.
VENTILATION (continued) Any ventilation fitted must comply with BS 5871 part 4 and BS 5440 part 2. Ventilation fitted under, or within immediate vicinity of the appliance must not be used as it may adversely effect performance of the ODS system. The appliance MUST NOT be installed in a bedroom, bathroom or any sleep- ing area.
FIXING THE APPLIANCE F860059 ISSUE A - 25/5/06 POSITION SPIRIT LEVEL ALONG THIS EDGE TO LEVEL WALL MOUNTED P23G & P23E TEMPLATE BEFORE MARKING OUT WALL FITTING TEMPLATE Do not block the ventilation holes of the appliance. The wall onto FIXING POINTS FOR GAS MODEL P23G FIXING POINTS FOR ELECTRIC MODEL P23E which the appliance is installed must be flat.
TESTING AND COMMISSIONING Turn on and test the gas supply up to the fire for any leaks, in accordance with the current edition of BS 6891 (natural gas installations) or BS 5482 pt1 (propane installations) . OPERATING THE APPLIANCE The pilot is visible behind the left hand side of the burner. ‘OFF’...
FITTING THE DECORATIVE FRAME ASSEMBLY Remove the decorative frame assembly from any protective packaging, and remove any pro- tective film that may be present on the frame. Attach the frame support brackets to the frame using two screws to retain each bracket. Note - the top frame support brackets are of a hooked design, and the lower brackets feature a hole.
10.1 SERVICING THE BURNER UNIT AND GAS ASSEMBLY Firstly, remove the decorative frame assembly per the reverse of section 8.4, the glass panel, and disconnect the gas connection inside appliance. The gas connections to the gas valve can now be released. Detatch the burn- er front cover plate by removal of the four retaining screws.
10.3 CATALYST (continued) Now divide the concentration of carbon monoxide (CO) expressed in percent by the concentration of carbon dioxide (CO2) to obtain the appliance combustion ratio. CO (%) CO2 (%) = ratio The combustion ratio of the gasses emitted by the catalytic convertor should not exceed 0.0015. If replacing, firstly, remove the decorative fireframe as described in section 8.4.
USER INSTRUCTIONS Section Content Page No Important Notes Clearances to Combustibles Ventilation & Room Size Operating Instructions Combustion Monitoring System Cleaning Servicing List of Replacement Parts IMPORTANT NOTES The installation and Servicing of this fire MUST only be carried out by a competent person (such as a Gas Safe registered fitter) in accordance with the Gas Safety (Installation and Use) Regulations 1998, the relevant British Standards, Codes of Practice, the Building Regulations and the manufacturer's instructions.
CLEARANCES TO COMBUSTIBLES Clearances to combustible materials Combustible materials are defined as wood, fabrics, or other materials likely to combust if exposed to flame. Generally, any material, which is likely to discolour, melt or misshape when exposed to moderate heat, should be considered as a combustible material or surface.
VENTILATION AND ROOM SIZE Purpose provided ventilation of 100cm 2 is required for this appliance. An openable window or equivalent is also required. The appliance should not be installed within 500mm of any air vent. Any ventilation fitted must comply with BS 5871 part 4 and BS 5440 part 2. Ventilation fitted under, or within immediate vicinity of the appliance must not be used as it may adversely effect performance of the combus- tion monitoring system (ODS) system.
CLEANING Before carrying out any of the following operations, ensure that the appliance is OFF and completely cold. GLASS PANEL - This can be cleaned with a suitable glass cleaner, or proprietary ceramic hob cleaner. Test on a small area first. PAINTED AREAS - These can be cleaned using a dry cloth.