Function Settings - Mitsubishi Electric PSH-P-GAH Installation Manual

Hide thumbs Also See for PSH-P-GAH:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
6. Electrical work
2
3 4
1
TEMP.
ON/OFF
F
MENU
ON/OFF
FILTER
E
BACK
MONITOR/SET
DAY
CHECK
PAR-21MAA
CLOCK
OPERATION
CLEAR
G
C
D
4
1
Fig. 6-2
Function table
Select unit number 00
Mode
Power failure automatic recovery
Indoor temperature detecting
LOSSNAY connectivity
Power voltage
Auto mode (only for PUHZ)
Select unit numbers 01 to 03 or all units (AL [wired remote controller]/07 [wireless remote controller])
Mode
Filter sign
Fan speed
No. of air outlets
Installed options (high-performance filter)
Up/down vane setting
Energy saving air flow
(Heating mode)
*1 When the power supply returns, the air conditioner will start 3 minutes later.
*2 Power failure automatic recovery initial setting depends on the connecting outdoor unit.
⁄ Mode number
1
⁄ Setting number
2
⁄ Refrigerant address
3
⁄ Unit number
4
A
TEST
B
1
2
Settings
Not available
Available
Indoor unit operating average
Set by indoor unit's remote controller
Remote controller's internal sensor
Not Supported
Supported (indoor unit is not equipped with outdoor-air intake)
Supported (indoor unit is equipped with outdoor-air intake)
240 V
220 V, 230 V
Energy saving cycle automatically enabled
Energy saving cycle automatically disabled
Settings
100 Hr
2500 Hr
No filter sign indicator
Standard (PLH/PLA)/Silent (PCH/PCA)
High ceiling 1 (PLH/PLA)/Standard (PCH/PCA)
High ceiling 2 (PLH/PLA)/High ceiling PCH/PCA)
4 directions
3 directions
2 directions
Not supported
Supported
No vanes
Equipped with vanes (vanes angle setup 1)
Equipped with vanes (vanes angle setup 2)
Disabled
Enabled

6.2. Function settings

6.2.1. Function setting on the unit (Fig. 6-2)
Changing the power voltage setting
• Be sure to change the power voltage setting depending on the voltage used.
1 Go to the function setting mode.
Switch OFF the remote controller.
Press the A and B buttons simultaneously and hold them for at least 2
seconds. FUNCTION will start to flash.
2 Use the C button to set the refrigerant address (3) to 00.
3 Press D and [--] will start to flash in the unit number (4) display.
4 Use the C button to set the unit number (4) to 00.
5 Press the E MODE button to designate the refrigerant address/unit number. [--]
will flash in the mode number (1) display momentarily.
6 Press the F buttons to set the mode number (1) to 04.
7 Press the G button and the current set setting number (2) will flash.
Use the F button to switch the setting number in response to the power supply
voltage to be used.
Power supply voltage
240 V
: setting number = 1
220 V, 230 V : setting number = 2
8 Press the MODE button E and mode and the setting number (1) and (2) will
change to being on constantly and the contents of the setting can be confirmed.
9 Press the FILTER A and TEST RUN B buttons simultaneously for at least two
seconds. The function selection screen will disappear momentarily and the air
conditioner OFF display will appear.
6.2.2. Function setting on the remote controller
Refer to the indoor unit operation manual.
Mode no.
01
*1
02
03
04
05
Mode no.
07
08
09
10
11
12
Setting no. Initial setting
Setting
1
*2
2
*2
1
2
3
1
2
3
1
2
1
2
Setting no. Initial setting
Setting
1
2
3
1
2
3
1
2
3
1
2
1
2
3
1
2
9

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Psa-rp-ga

Table of Contents