2
Specifications

ELECTRICAL DATA

RKS+FCQ35B
RKS+FCQ50B
RKS+FCQ60B
* This information was not available at the time of publication.
RKS+FHQ35B
Indoor unit
Outdoor unit
FHQ35BUV1B
RKS35BVMB
RKS+FHQ50B
RKS+FHQ60B
Indoor unit
Outdoor unit
FHQ50BUV1B
RKS50BVMB
FHQ60BUV1B
RKS60BVMB
RKS+FBQ35B
RKS+FBQ50B
RKS+FBQ60B
* This information was not available at the time of publication.
SYMBOLS
MCA
: Min. Circuit Amps (A)
MFA
: Max. Fuse Amps (A)
RHz
: Rated operating frequency (Hz)
RLA
: Rated Load Amps (A)
OFM
: Outdoor Fan Motor
IFM
: Indoor Fan Motor
FLA
: Full Load Amps
W
: Rated motor output (W)
• Pair Application • R-410A • RKS25-35-50-60-71BVMB
Power supply
Hz-Volts
Voltage range
MAX. 50Hz 253V
50-230
MIN. 50Hz 207V
Power supply
Hz-Volts
Voltage range
MAX. 50Hz 253V
50-230
MIN. 50Hz 207V
MAX. 50Hz 253V
50-230
MIN. 50Hz 207V
• Split - Sky Air • Outdoor Units
Compressor
MCA
MFA
RHz
RLA
15
15
78
4.91
Compressor
MCA
MFA
RHz
RLA
18
20
79
7.5
18
20
90
8.84
NOTES
1. RLA is based on the following conditions:
Indoor temp.: 27°CDB/19.0°CWB
Outdoor temp. : 35°CDB
2. Maximum allowable voltage unbalance between phases is 2%
3. Select wire size based on the larger value of MCA.
4. Instead of fuse, use circuit breaker.
OFM
IFM
W
FLA
W
FLA
19
0.35
62
0.6
3D040596
OFM
IFM
W
FLA
W
FLA
53
0.18
62
0.6
53
0.24
62
0.6
3D040597