Tips and tricks

Programming the next day(s)
After confirming the programmed actions of a specific day (i.e. after
pressing the < button for 5 seconds), press the pr button once. You
can now select another day by using the pi and pj buttons
and restart consulting and programming.
Copying programmed actions to next day
In heating/cooling program it is possible to copy all programmed
actions of a specific day to the next day (e.g. copy all programmed
actions from "1" to "2").
To copy programmed actions to the next day, proceed as follows:
1
Press the < button.
The actual mode is blinking.
Use the pi and pj buttons to select the mode you want
2
to program.
The selected mode is blinking.
You can leave programming by pressing the pr button.
Press the < button to confirm the selected mode.
3
The actual day is blinking.
4
Select the day you would like to copy to the next day by means
of the pi and pj buttons.
The selected day is blinking.
You can return to step
2
5
Press the < and pr buttons simultaneously for 5 seconds.
After 5 seconds the display will show the next day (e.g. "2" if
"1" was selected first). This indicates that the day has been
copied.
You can return to step
2
Deleting one or more programmed actions
Deleting one or more programmed actions is done at the same time
as storing the programmed actions.
When all actions for one day have been programmed, make sure that
the display shows the highest action number you would like to save.
By pressing the < button for 5 seconds, you store all actions except
those with a higher action number than the one that is displayed.
E.g. when the < button is pressed when action number 3 is
displayed, actions 1, 2 and 3 are stored but 4 and 5 are deleted.
Deleting a mode
Press the < button.
1
The actual mode is blinking.
2
Use the pi and pj buttons to select the mode you want
to delete (quiet mode
heating
w
).
The selected mode is blinking.
3
Press the < and ba button simultaneously for 5 seconds to
delete the selected mode.
Deleting a day of the week (cooling or heating mode)
1
Use the = button to select the operation mode (cooling or
heating) you want to delete.
Press the < button.
2
The actual mode is blinking.
Press the < button to confirm the selected mode.
3
The actual day is blinking.
4
Select the day you would like to delete by means of the pi
and pj buttons.
The selected day is blinking.
Press the < and ba button simultaneously for 5 seconds to
5
delete the selected day.
EKHBH/X016AA
Indoor unit for air to water heat pump and sanitary warm water tank for air to water heat pump system
4PW36977-1B
by pressing the pr button.
by pressing the pr button.
s
, booster heating
m
or sanitary
F
IELD SETTINGS
The indoor unit should be configured by the installer to match the
installation environment (outdoor climate, installed options, etc.) and
user demand. Thereto, a number of so called field settings are
available. These field settings are accessible and programmable
through the user interface on the indoor unit.
Each field setting is assigned a 3-digit number or code, for example
[5-03], which is indicated on the user interface display. The first digit
[5] indicates the 'first code' or field setting group. The second and
third digit [03] together indicate the 'second code'.
A list of all field settings and default values is given under
settings table" on page
15. In this same list, we provided for 2
columns to register the date and value of altered field settings at
variance with the default value.
A detailed description of each field setting is given under
description" on page
11.

Procedure

To change one or more field settings, proceed as follows.
3
2
Press the z button for a minimum of 5 seconds to enter FIELD
1
SET MODE.
The $ icon (3) will be displayed. The current selected field
setting code is indicated ; (2), with the set value displayed to
the right - (1).
Press the bgi button to select the appropriate field
2
setting first code.
Press the bgj button to select the appropriate field
3
setting second code.
4
Press the pfi button and pfj button to change
the set value of the select field setting.
5
Save the new value by pressing the pr button.
6
Repeat step 2 through 4 to change other field settings as
required.
7
When finished, press the z button to exit FIELD SET MODE.
Changes made to a specific field setting are only
NOTE
stored when the pr button is pressed. Navigating to a
new field setting code or pressing the z button will
discard the change made.
"Field
"Detailed
1
Operation manual
10

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ekhbx016aa

Table of Contents