INTRODUCTION
The Muster
Alarm Panel (M2AP01) is an advanced integrated control for the monitoring, control and activation of
II
Muster
Fire Suppression Systems. Used in conjunction with the various Muster
II
detectors this provides a flexible and complete solution to fire protection.
Features:
Integrated battery provides a minimum of 2 years operation – no external power connection required
Allows precise measurement of cylinder pressures to 0.1 bar
Integrated manual activation button with tamper seal (MusterWire LHD installations only)
Universal - can be used on both LOP and electrical detection installations
Solid anodised aluminum construction with IP66 protection
Extended operating range of -40 to +70°C (Celsius)
Circular design in conjunction with the universal stainless steel bracket allows easy orientation at any angle as well
as in-dash mounting
Loud 98 dB buzzer
Ultra bright LED indicators with dim function for low light conditions
Data logging of events with time and date stamps
Data port allows firmware upgrades in the field
ALARM, FAULT and SHUTDOWN relay outputs with selectable N/O or N/C contacts
Two-wire system allows for easy wiring of all circuits using the two core silicone cable and the tool-less IP68 splices
ISOLATED mode allows safe maintenance and provides advanced test functions for easy maintenance and fault
finding
Advanced circuit design combines pressure reading and cylinder activation on a single pair of wires
Expandable – addressable circuit design allows the system to be expanded to include functions such as hydraulic
pressure relief or advanced GSM telemetry
pressure transducers, actuators and
II
Page 5