OPERATION

MusterWire LHD Alarm Panel Configuration
The panel operates in a number of possible states depending on the conditions and settings:
Isolated Mode - system is isolated (only available on MusterWire LHD installations)
 
Standby Mode - system is functioning correctly
 
Fault Mode - a fault has been detected
 
Fire Mode - a FIRE has been detected
 
LED INDICATORS
For the majority of the time the Alarm Panel is in a low power state and will only blink the appropriate indicator
briefly every three seconds. This is essential to keep the battery life to a maximum. On detection of a fire however the
appropriate LED's will flash brightly for maximum effect. Note that even in fire mode the panel will revert to a low power
state after 15 minutes.
DIM FUNCTION: The SHUTDOWN DELAY button serves an additional non-conflicting function of dimming the led
indicators should they prove to be a nuisance in low light conditions – this dim mode is automatically exited after two
hours or on request by re-pressing the button.
AUDIBLE BUZZER
The built in buzzer gives a brief pip every three seconds if there are any system faults and a loud alarm in event of a fire.
At most stages the buzzer can be toggled on and off with the MUTE button. Note that the MUTE function is disabled if
there is no fault or alarm and automatically resets itself on any new event. This ensures that no event can go unnoticed.
TEST FUNCTION: The TEST button serves various functions depending what state the panel is in. Refer to the various
modes below for detailed behavior.