Failsafe Relay Specifications; Copper Serial Port Specifications; Copper Ethernet Port Specifications - Siemens RUGGEDCOM RX1500 Installation Manual

Hide thumbs Also See for RUGGEDCOM RX1500:
Table of Contents

Advertisement

Chapter 4
Technical Specifications
Section 4.2

Failsafe Relay Specifications

Maximum Switching Voltage
30 VDC
250 VAC
Section 4.3

Copper Serial Port Specifications

Baud Rate
1200 to 230400 kbps
Section 4.4

Copper Ethernet Port Specifications

The following details the specifications for copper Ethernet ports that can be ordered with the RX1500.
d
Speed
10/100/1000TX
10/100/1000TX
10/100/1000TX
10/100/1000TX
10/100/1000TX
10/100TX
10/100TX
10/100TX
10/100TX
10/100TX
d
Auto-negotiating.
e
Shielded or unshielded.
40
Connector
RJ45
8-Pin A-Coded M12
8-Pin A-Coded M12
Controlled Bypass
8-Pin X-Coded M12
8-Pin X-Coded M12
Controlled Bypass
RJ45
8-Pin A-Coded M12
8-Pin A-Coded M12
Controlled Bypass
4-Pin A-Coded M12
4-Pin A-Coded M12
Controlled Bypass
Rated Switching Current
5 A
6.25 A
Connector
RJ45
Cable
d
Mode
Duplex
FDX/
> CAT-5
HDX
FDX/
> CAT-5
HDX
FDX/
> CAT-5
HDX
FDX/
> CAT-5
HDX
FDX/
> CAT-5
HDX
FDX/
> CAT-5
HDX
FDX/
> CAT-5
HDX
FDX/
> CAT-5
HDX
FDX/
> CAT-5
HDX
FDX/
> CAT-5
HDX
Isolation
2800 VDC for 1 minute
Isolation
2500 VDC for 1 minute
f
Wiring Standard
e
Type
TIA/EIA T568A/B
TIA/EIA T568A/B
TIA/EIA T568A/B
TIA/EIA T568A/B
TIA/EIA T568A/B
TIA/EIA T568A/B
TIA/EIA T568A/B
TIA/EIA T568A/B
TIA/EIA T568A/B
TIA/EIA T568A/B
Failsafe Relay Specifications
RUGGEDCOM RX1500
Installation Guide
Maximum
g
Isolation
Distance
100 m
1.5 kV
(328 ft)
100 m
1.5 kV
(328 ft)
100 m
1.5 kV
(328 ft)
100 m
1.5 kV
(328 ft)
100 m
1.5 kV
(328 ft)
100 m
1.5 kV
(328 ft)
100 m
1.5 kV
(328 ft)
100 m
1.5 kV
(328 ft)
100 m
1.5 kV
(328 ft)
100 m
1.5 kV
(328 ft)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ruggedcom rx1512

Table of Contents