Special Installation & Operating Instructions - Keltech C2N363/600D Installation Manual

Tankless heater models c2n series
Table of Contents

Advertisement

C2N Series Tankless Heater
Special Installation and Operating Instructions
Tankless Water Heaters With Optional Class I Division 2 Purge EXP2 Option
General Information
All Keltech Tankless Water Heaters with a model number suffix of – EXP2 have been fitted with a Z purge system to
pressurize the enclosure suitable for use in Class I Division 2 Hazardous Locations .
A Continuous Flow (Model CF) Mini-Z Pressurizing System has been fitted to the bottom of the enclosure .
2
4
EXP2 Installation Notes
1 . Any tubing, conduit or fittings connected to the Pressurized Enclosure (PE) must conform to local codes for
flammability ratings .
2 . All egress into PE must be plugged and properly sealed to minimize leakage of purge air . Use hazardous
location sealing fittings suitable for Class I locations within 18" (458mm) of enclosure .
3 . The EXP2 purge system option is a continuous flow purge system and is calibrated to flow at 0 .9 SCFM
(1 .5291 CMH) . To minimize waste, plug and seal all openings and conduit .
4 . The system is designed for use primarily with compressed air . The source of the compressed air must be
from a non-classified area (see Purge Gas Supply Notes) . Purge air must be clean, dry and free of flammable
gases . When inert compressed gases are used (Nitrogen, for example) the installer and facility manager must
take suitable precautions on-site so that buildup of the inert gas does not present a health hazard . Where risk
of asphyxiation exists, a warning label must be fitted to the Pressurized Enclosure (PE) .
5 . Adjustment of Purge System is not necessary . System is fully calibrated .
6 . Connect to Purge System where indicated . Connection port is 1/4" NPT female . Supply pressure must be
regulated to 60–115 PSI (4-8 bar) .
14
Purge System
Relief Valve
1
2
3
4
5
Conduit Hub
Class 1 Div . 2
supplied by others
5"
1
(127mm)
18" (458mm)Max
5
Explosion proof
sealing fitting
supplied by others
5/3/2016
Suggested region for power
1
entrance at left/bottom of enclosure .
Entrance hole and components to
be provided by installer .
Purge Control Panel
2
Class 1 Division 2
All installation egress from
3
panel must be sealed (electrical
conduit) for proper explosion proof
installation .
Spark arrestor with calibration orifice
4
is located behind the purge control
unit and through the bottom of the
enclosure .
Purge gas/compressed air inlet
5
fitting here .
Bradley • 215-1821 Rev. B; ECN 16-17-005
Installation

Advertisement

Table of Contents
loading

Table of Contents