Operational Tests - Keltech C2N363/600D Installation Manual

Tankless heater models c2n series
Table of Contents

Advertisement

C2N Series Tankless Heater
7
Perform Operational Test No. 1
Ensure the enclosure door is closed
prior to performing operation test.
A
Set the 3-pole switch or circuit breaker to the
ON position .
Start the water flow through the heater by
B
starting the process or fixture this heater is
connected to in order to activate heater .
When flow rate reaches approximately
0 .75gpm/2 .8 lpm (standard), the flow switch
activates and begins the heating process .
When the flow switch activates:
• Phase indicator lights illuminate on the front
C
bezel verifying power supply connection to the
heating elements via the solid-state relays .
• Element load lights may be solid or flash
in unison as heating elements modulate
depending on the hot water demand .
• Lower display on controller goes from off
to setpoint temperature .
8
Perform Operational Test No. 2
Each model has precise specifications for temperature rise capabilities.
A
Turn on hot water faucet/fixture/process . The
heater should activate immediately .
If the water flow exceeds maximum heating capacity of the heater, the temperature of water at the outlet
may be lower than the temperature selected on the controller. See table below to determine maximum
temperature rise capabilities.
Models 480/600V
kW
C2N36
36
C2N50
50
Models 480/600V
kW
C2N36
36
C2N50
50
10
Temperature Rise (GPM & F°)
1 gpm
2 gpm
3 gpm
4 gpm
ΔT °F
ΔT °F
ΔT °F
ΔT °F
122
82
170
113
Temperature Rise (lpm & C°)
3 .8 lpm
7 .6 lpm
11 .4 lpm
15 .1 lpm
ΔT °C
ΔT °C
ΔT °C
ΔT °C
50
46
94
63
5/3/2016
Press the up or down arrow keys to
D
adjust the set temperature . The controller
displays the temperature of water
measured at the outlet .
Located on the panel are two 36kW-50kW
green ready lights. When illuminated, the
safety circuit is engaged and ready for use.
Test water temperature and stability at
E
outlet by viewing the display . Controller
displays (in red) the temperature of water
exiting the heater .
Heater will not energize heating elements if the
inlet water temperature is equal to or greater than
the temperature set on the digital controller .
Turn off hot water faucet/fixture/process .
B
The flow switch will deactivate and shut
off power to the heater .
5 gpm
6 gpm
7 gpm
ΔT °F
ΔT °F
ΔT °F
62
50
40
34
85
68
57
48
*May exceed the maximum temperature setting of the heater
18 .9 lpm
22 .7 lpm
26 .5 lpm
ΔT °C
ΔT °C
ΔT °C
34
28
22
19
47
38
32
27
8 gpm
9 gpm
10 gpm
ΔT °F
ΔT °F
ΔT °F
30
26
24
43
38
34
30 .2 lpm
34 .1 lpm
37 .8 lpm
ΔT °C
ΔT °C
ΔT °C
17
14
13
24
21
19
Bradley • 215-1821 Rev. B; ECN 16-17-005
Installation
11 gpm
12 gpm
ΔT °F
ΔT °F
22
20
31
8
41 .6 lpm
45 .4 lpm
ΔT °C
ΔT °C
12
11
17
16