Cable Entries; Dimensions, Weights And Noise; Input Power Connection - ABB ACS800-02 Hardware Manual

Acs800-02 drives (45 to 500 kw); acs800-u2 drives (60 to 600 hp)
Hide thumbs Also See for ACS800-02:
Table of Contents

Advertisement

Cable entries

Mains, motor and brake resistor cable terminal sizes (per phase), maximum
accepted cable diameters and tightening torques are given below . The maximum
allowed width of the cable lug is 38 mm.
Frame
size
Number of holes per
phase
R7
2
R8
3

Dimensions, weights and noise

Frame size
R7
R8
H
height without lifting lugs
W1 width of the basic unit
W2 width with the optional enclosure extension
W3 weight of the basic unit
W4 weight with the optional enclosure extension (basic configuration with switch fuse but without
contactor and other options).

Input power connection

Voltage (U
)
1
Prospective short-circuit
current (IEC 60439-1)
Frequency
Imbalance
Fundamental power factor
(cos phi
)
1
U1, V1, W1, U2, V2, W2, UDC+/R+, UDC-, R-
Cable Ø
mm
58
58
H
mm
1507
2024
208/220/230/240 VAC 3-phase ± 10 % for 230 VAC units
380/400/415 VAC 3-phase ± 10 % for 400 VAC units
380/400/415/440/460/480/500 VAC 3-phase ± 10 % for 500 VAC units
525/550/575/600/660/690 VAC 3-phase ± 10 % for 690 VAC units
For units without an enclosure extension: 65 kA (Icf).
For units with an enclosure extension:
Icw / 1 sec.
50 kA
US and Canada: The drive is suitable for use in a circuit capable of delivering not more than
65,000 symmetrical amperes (rms) at 600 V maximum.
48 to 63 Hz, maximum rate of change 17 %/s
Max. ± 3 % of nominal phase to phase input voltage
0.98 (at nominal load)
Screw
Tightening
torque
Nm
M12
50...75
M12
50...75
IP 21
W1
W2
Depth
mm
mm
mm
250
602
524
347
793
622
Ipk
105 kA
Earthing PE
Screw
Tightening
torque
M8
15...22
M8
15...22
W3
W4
kg
kg
100
195
230
375
Technical data
93
Nm
Noise
dB
71
72