Mechanical Installation; Operation - ABB ACS800-02 Hardware Manual

Acs800-02 drives (45 to 500 kw); acs800-u2 drives (60 to 600 hp)
Hide thumbs Also See for ACS800-02:
Table of Contents

Advertisement

8

Mechanical installation

These notes are intended for all who install the drive. Handle the unit carefully to
avoid damage and injury.

Operation

These warnings are intended for all who plan the operation of the drive or operate
the drive. Ignoring the instructions can cause physical injury or death or damage the
equipment.
Note:
Safety instructions
ACS800-01: The drive is heavy. Do not lift it alone. Do not lift the unit by the
front cover. Place the unit only on its back.
ACS800-02, ACS800-04: The drive is heavy. Lift the drive by the lifting lugs
only. Do not tilt the unit. The unit will overturn from a tilt of about 6 degrees.
Make sure that dust from drilling does not enter the drive when installing.
Electrically conductive dust inside the unit may cause damage or lead to
malfunction.
Ensure sufficient cooling.
Do not fasten the drive by riveting or welding.
Before adjusting the drive and putting it into service, make sure that the motor
and all driven equipment are suitable for operation throughout the speed range
provided by the drive. The drive can be adjusted to operate the motor at
speeds above and below the speed provided by connecting the motor directly
to the power line.
Do not activate automatic fault reset functions of the Standard Application
Program if dangerous situations can occur. When activated, these functions
will reset the drive and resume operation after a fault.
Do not control the motor with the disconnecting device (means); instead, use
the control panel keys
The maximum allowed number of charging cycles of the DC capacitors (i.e.
power-ups by applying power) is five in ten minutes.
If an external source for start command is selected and it is ON, the drive (with
Standard Application Program) will start immediately after fault reset unless the
drive is configured for 3-wire (a pulse) start/stop.
When the control location is not set to Local (L not shown in the status row of
the display), the stop key on the control panel will not stop the drive. To stop
the drive using the control panel, press the LOC/REM key and then the stop
key
.
and
, or commands via the I/O board of the drive.