Panel Installation; Pipe Installation; External Connections - GE Security FASD700 Installation Manual

Table of Contents

Advertisement

Note:

2.3 Panel installation

The panel should be secured to a suitable surface using the 4 corner fixing points.

2.4 Pipe installation

Note the following:

2.5 External connections

The panels allow the following external connections.
2.5.1 FASD710 / FASD712 panels
2.5.2 FASD715 / FASD717 panels
7
For detector connection details and for alarm / end-of-line resistor values refer to the
detector / fire panel manual.
In the event of a fault on the FASD710 / FASD712 panel, the relay on the main PCB
will open the fault monitor line "DET1". This will give the fault signal on the fire panel.
For pipe installation guidelines refer to the FHSD700 Ducts Installation
manual.
ABS, UPVC, copper or stainless steel pipe may be used.
Pipe with an outer diameter of 25 mm or 26.7 mm may be used. An adapter is
required for used with 25 mm pipe.
Pipe lengths are cut as required and joined by sockets (permanent), solvent welded
or socket unions (removable).
Smoke tests should be performed before planning and installing the pipe network.
CAUTION! Do not use T-joints in low-pressure wide-bore systems. These
make pipe design and air-flow calculation difficult to predict accurately.
Mains supply
24 VDC
External loop disconnect alarm relay (optional)
I/O module (optional)
Mains supply
24 VDC
Alarm relays
RS232
Isolate
External loop disconnect alarm relay (optional)
I/O module (optional)
WWW.UKPANELS.COM
FASD700 aspirated smoke detectors – Installation manual