Configuration; Electrical Data - Carrier 38LF048 Installation, Start-Up And Service Instructions Manual

38lb/38lf air cooled condensing unit
Table of Contents

Advertisement

Configuration

Unit is shipped from factory in vertical discharge configuration as standard. However, converting to horizontal
discharge as shown is simply effected without extra fittings or metal sheet work.
To modify into horizontal discharge mode :
1. Ensure all electrical supply to the unit is disconnected and then loosen top and fan discharge
panels by removing screws.
Release wires tie on fan motor wires in control box and ease wires out of hole for extra length for
2.
interchanging panels.
Assemble top panel on front of unit and secure with screws.
3.
Final assembles fan discharge panel. Pull fans motor wires taut and retie extra length in control
4.
box.
Check fan for free rotation and observe that wiring has not been damaged or improperly strained.
5.

Electrical Data

Unit Model
Power Supply
38LF048
380V/3Ph/50Hz
38LF060
380V/3Ph/50Hz
38LF007
380V/3Ph/50Hz
38LF009
380V/3Ph/50Hz
38LF012
380V/3Ph/50Hz
38LF015
380V/3Ph/50Hz
Voltage Range
Compressor
Min
Max
RLA
342
415
7.4
342
415
8.9
342
415
10.9
342
415
16.0
342
415
17.7
342
415
26.5
- 5 -
Fan Motor
LRA
QTY
RLA
52.0
1
1.49
74.0
1
1.49
101.0
1
2.00
118.0
1
2.00
118.0
1
3.92
174.0
1
3.92
Recommended
Power
Ground Wire
Field CB (AT)
Wire(mm.2)
(mm.2)
4
2.5
20
4
2.5
20
6
4
25
6
4
30
10
4
40
16
4
50

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents