Hisense RS-09DC4S Series Service Manual page 8

Table of Contents

Advertisement

5) There is something
that blocked the liquid
cycle system
2.NO COOL
(Popular failure reasons are below):
Reason
1) Leakage of gas
2)There is some thing
that blocked the liquid
cycle system
see if it is normal.
b, higher temperature of compressor
surface.
C, cut off the discharging tube, to see if you
can block the gas coming out of the tube
when compressor is working.
Some time there is something blocked the
filter of liquid cycle system, so that unit is not
cold.
Phenomenon of failure:
a, lower pressure of discharging
b, lower temperature of discharging.
analysis
Phenomenon of failure:
a, leaking fast
b, leaking slowly
c, no voice of liquid flowing
d, cut off charging tube, no gas
goes out.
A, Ice blocking
Sometime because unknown
reason water comes into liquid
cycle system, the capillary will be
blocked by water after unit runs for
period of time.
Phenomenon of failure:
The unit works well in the
inception, after period of time the
ice appears in the capillary and
becomes more and more, till
blocks the hole of capillary
completely. In the moment you
can find the ice on the evaporator
defrosts. The noise of liquid flow
disappears. The pressure of
absorbing becomes negative.
The phenomenon above will
appear again and again.
The way to check ice blocking:
Warm the capillary with a hot
towel, after a while the ice in the
capillary melt, you can hear a
sound of gas flow comes from the
capillary abruptly. The pressure of
absorbing becomes higher. It is
Ice blocking.
Change a new filter
Solutions:
First find out the point of leaking on tube,
and then sealed it, vacuuming it, finally
recharge with gas.
Note:
If you find oil on somewhere, it is possible
that leakage point is there.
First stop unit for several minutes, and then
open charging tube, discharge all of gas.
Blow the cycle system with gas of nitrogen,
and then recharge Gas, finally sealed the
system.