Section 3: Site Selection and Preparation

Site Selection
Allow sufficient room on all sides of the
generator for maintenance and servicing.
Clearance from the ends and front of the
generator must be 3 ft m (0.91). This includes
shrubs, bushes and trees. Clearance from the
back of the generator must be a minimum of 18
in (457 mm). Clearance at the top should be a
minimum of 5 ft (1.52 m) from any structure,
overhang or projections from the wall.
DO NOT install under wooden decks or
structures unless there is at least 5 ft (1.52 m)
of clearance above the generator.
Install the generator set, in its protective enclosure,
outdoors, where adequate cooling and ventilating air is
always available
(Figure
The installation of the generator must comply
strictly with NFPA 37, NFPA 54, NFPA 58 and
NFPA 70 standards.
Install the unit where air inlet and outlet openings
will not become obstructed by leaves, grass, snow,
etc. If prevailing winds will cause blowing or
drifting, consider using a windbreak to protect the
unit.
Installation Guidelines For 60 Hz Air-cooled Generators
No operable windows or openings in the wall permitted
within 1.52 m (5 ft) from any point of the generator.
5 ft
Minimum Distance
(1.52 m)
3 ft (0.91 m)
Top of Generator
NOTE: Removable fence panels for servicing
cannot be placed less than 457 mm (18 in) in
front of the generator.
Figure 3-1. Installation Guidelines
3-1). Consider these factors:
Section 3: Site Selection and Preparation
18 in (457 mm)
3 ft (0.91 m)
Install the generator on high ground where water
levels will not rise and endanger it. It should not
operate in or be subjected to standing water.
Allow sufficient room on all sides of the generator
for maintenance and servicing. This unit must be
installed in accordance with any codes that are in
place in your country or local jurisdiction for
minimum distances from other structures.
Clearance from the ends and front of the generator
must be 3 ft (0.91 m). This includes shrubs, bushes
and trees. Clearance from the back of the
generator must be a minimum of 18 in (457 mm).
Existing Wall
5 ft
(1.52 m)
3 ft (0.91 m)
These guidelines are based upon fire testing of
the generator enclosure and the manufacturer's
requirement for air flow for proper operation.
Local codes may be different and more restrictive
than what is described here.
5 ft (1.52 m)
Minimum Distance
5 ft (1.52 m)
Minimum Distance
Clearance from operable windows,
doors or any openings in the wall.
000607