Figure 17: Finish Screen - Unitronics GW-BAC1 User Manual

Bacnet gateway for interfacing unitronics plcs to building automation systems: bacnet ms/tp, bacnet/ip, modbus/tcp.
Table of Contents

Advertisement

Unitronics's BACnet Gateway User Guide
Finish: This window will show the addressing map of the data to be read/write from/to the device -to be use
in VisiLogic ladder logic- and will let you export the configuration file that you will download to the GW-BAC1
via the GUI browser.
Once you have created the configuration file, it has to be downloaded to the GW-BAC1 unit according to
the following instructions.
a.
Connect a standard CAT5 Ethernet cable (Straight through or Cross-Over) between the PC and GW-
BAC1
b. The Default IP Address of GW-BAC1 is 192.168.1.24, Subnet Mask is 255.255.255.0. If the PC and
GW-BAC1 are on different IP Networks, assign a static IP Address to the PC on the 192.168.1.xxx
network
c.
Go to
d. Right-click on Local Area Connection > Properties
e.
Highlight
f.
Select: Use the following IP address
g.
Click
Unitronics

Figure 17: Finish Screen

>
>
>
twice
Page 16 of 28