CASSETTE TYPE
Model
Heating capacities are based on conditions below.
CS-A43BB4P
3 phase, 50Hz, 400V
Heating capacity
Indoor temperature 20°C D.B.
14.0 kW
Outdoor temperature 7°C D.B. 6°C W.B.
Standard air volume 30m
Inlet Air
External Static
Entering Air
Pressure (Pa) Air
Dry Bulb (°C)
3
Volume (m
/min)
30
Inlet Air
External Static
Entering Air
Pressure (Pa) Air
Dry Bulb (°C)
3
Volume (m
/min)
30
3
/min
Outdoor Temperature (°C W.B.)
-6
0
H.C.
H.C.
H.C.
15
10.2
12.3
14.7
20
9.66
11.6
14.0
25
9.10
110.9
13.3
Outdoor Temperature (°C W.B.)
-6
0
IPT
IPT
IPT
15
2.87
3.28
3.90
20
3.03
3.49
4.10
25
3.20
3.69
4.31
Model
CS-A50BB4P
Heating capacity
15.5 kW
6
12
External Static
Pressure (Pa) Air
H.C.
Volume (m
17.1
16.8
31
16.1
6
12
External Static
Pressure (Pa) Air
IPT
Volume (m
4.59
5.00
31
5.60
H.C. = Heating Capacity
IPT = Power Consumption
62
Heating capacities are based on conditions below.
3 phase, 50Hz, 400V
Indoor temperature 20°C D.B.
Outdoor temperature 7°C D.B. 6°C W.B.
Standard air volume 31m
Inlet Air
Outdoor Temperature (°C W.B.)
Entering Air
-6
Dry Bulb (°C)
H.C.
3
/min)
15
11.3
20
10.7
25
10.08
Inlet Air
Outdoor Temperature (°C W.B.)
Entering Air
-6
Dry Bulb (°C)
IPT
3
/min)
15
3.48
20
3.68
25
3.88
3
/min
0
6
12
H.C.
H.C.
H.C.
13.6
16.3
18.9
12.8
15.5
18.6
12.1
14.7
17.8
0
6
12
IPT
IPT
IPT
3.98
4.72
5.57
4.22
4.97
6.06
4.47
5.22
6.60