3-3.Tools

3-3-1. Required Tools

The service port diameter of packed valve of the outdoor unit in the air-water heat pump using R410A is
changed to prevent mixing of other refrigerant.
To reinforce the pressure-resisting strength, fl are processing dimensions and opposite side dimension of fl are
nut (For Ø12.7 copper pipe) of the refrigerant piping are lengthened.
The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge,
clogging of capillary, etc. Accordingly, the tools to be used are classifi ed into the following three types.
1. Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))
2. Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)
3. Tools commonly used for R410A and for conventional refrigerant (R22)
The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifi cations are changed for R410A and their interchangeability
No.
Used tool
1
Flare tool
Copper pipe gauge for
2
adjusting projection margin
3
Torque wrench (For Ø12.7)
4
Gauge manifold
5
Charge hose
6
Vacuum pump adapter
Electronic balance for
7
refrigerant charging
8
Refrigerant cylinder
9
Leakage detector
10
Charging cylinder
(Note 1) When fl aring is carried out for R410A using the conventional fl are tools, adjustment of projection
margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.
(Note 2) Charging cylinder for R410A is being currently developed.
In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary as
the general tools.
1. Vacuum pump
Use vacuum pump by attaching vacuum pump adapter.
2. Torque wrench (For Ø6.35, Ø9.52)
3. Pipe cutter
5. Pipe bender
7. Screwdriver (+, –)
Also prepare the following equipments for other installation method and run check.
1. Clamp meter
2. Thermometer
Usage
Pipe fl aring
Flaring by conventional
fl are tool
Connection of fl are nut
Evacuating, refrigerant
charge, run check, etc.
Vacuum evacuating
Refrigerant charge
Refrigerant charge
Gas leakage check
Refrigerant charge
General tools (Conventional tools can be used.)
4. Reamer
6. Level vial
3. Insulation resistance tester
4. Electroscope
– 13 –
R410A air-water heat pump installation
Existence of
Whether conventional
new equipment
equipment can be used
for R410A
Yes
*(Note 1)
Yes
*(Note 1)
Yes
Yes
Yes
Yes
Yes
Yes
(Note 2)
8. Spanner or Monkey wrench
9. Hole core drill (Ø65)
10. Hexagon wrench (Opposite side 4mm)
11. Tape measure
12. Metal saw
Conventional air-water
heat pump installation
Whether new equipment
can be used with
conventional refrigerant
*(Note 1)