Napoleon NZ6000-1 Installation And Operating Instructions Manual page 31

Table of Contents

Advertisement

C.
Connect the 6" (152.4mm) collar to the blower opening located on the side of the appliance. An
optional opening is covered on the other side of the appliance. If this location is preferred, switch the
cover plate and collar.
Secure by reaching through the collar and bending the tabs.
Use sealant to ensure that the connection is air tight.
We recommend installing the blower in a different room or
even different level of the house. This will generate greater air
movement and improve the distribution of the warm air com-
ing from the appliance.
D.
Electrical Connection
a) Remove the junction box covers on the
appliance and the blower.
b) Removing the junction box cover on the
appliance exposes 4 black, labeled wires:
Two wires labelled "by-pass" - go to by-pass
(summer) switch (not supplied - overrides the
thermally activated switch enabling the user to
run the blower without heat).
IMPORTANT: Marrett by-pass (summer)
switch wire leads separately (do not connect
together), if the by-pass switch is not
desired.
One wire labelled "blower" - connects to
KB-35 rheostat (not supplied) and then fan-
speed control blower wire connects to white
blower wire.
One wire labelled "L1" - connects to power
(hot lead).
c) Removing the junction box cover on the
blower exposes 3 coloured wires:
One black wire - connects to power "L2"
(neutral lead).
One green wire - connects to ground.
One white wire - connects to fan-speed
control rheostat (not supplied) See above.
BY-PASS
(SUMMER)
SWITCH
NOT SUPPLIED
THERMODISC
FAN-SPEED CONTROL
(RHEOSTAT {VARIABLE SPEED SWITCH})
or WALL SWITCH or THERMOSTAT
NOT SUPPLIED
31
PRESSURE
SWITCH
L1
G
L2
FAN