Installation Information; Earth Connection - impro XEC900 Installation Manual

Impro (ecii) ethernet controller
Table of Contents

Advertisement

INSTALLATION INFORMATION

Accessories
Find the following when unpacking the Impro EC
Either, an Impro EC
Aluminium extruded Cabinet. The Cabinet consists of a Top Cover and a Base
sealed at each end with a Mild Steel End Plate, secured with 5 Thread Cutter
Screws (M3 x 8 mm).
Or, an Impro EC
Cabinet. The Cabinet consists of a hinged Lid and a Base.
A 3 V, CR2032, Lithium cell Battery.
A 6 V 3 Ahr Sealed Lead Acid Backup Battery.
Four Combi Screws (No. 4 x 10 mm) (IPS970 Only).
A glass Fuse, Slow Blow, 3.15 A, 250 V (5 mm x 20 mm) (IPS970 Only).
A MAC Address Label.
An extra Fixed Address Label.
General
Remember the following when installing your Impro EC
Communications Distance
RS485 1 (Controller Port) and RS485 2 (Terminal Port)
The RS485 communications distance between the Impro EC
Impro Unit in a cable run, MUST NOT exceed 1 km (1 090 yd). Achieve this by using
good quality screened twisted pair Mylar cable, EARTHED on one side.
Ethernet Port
The Ethernet Controller plugs into an Ethernet Switch or Hub (or other network device),
cable runs for this must conform to Ethernet cabling specifications.
Termination Resistors for RS485 Bus Communications
Long transmission lines or multiple "star" connections, may cause communication
problems. Placing the Terminating Resistor Jumper Link in the LAST UNIT AT THE
END OF THE CABLE RUN should solve the problem (depending on the bus). Refer to
Figure 1 on page 8.

EARTH Connection

In conditions where excessive noise is present connect the Impro EC
good EARTH point. Using either of the RS485 Ports, connect the EARTH Lead to the
"SHD" Terminal. Mains EARTH can be used, but electrical noise may persist. The
EARTH Lead to the Impro EC
2
of 1 mm
(0.001 in
XEC300-0-0-GB-09
II
Controller (XEC900) housed in a Black, powder-coated,
II
Controller (IPS970) housed in a Black Mild Steel, powder-coated
II
Controller should have a minimum cross-sectional area
2
) and can be either solid or stranded.
September 2015
II
Controller:
II
Blank Space
Controller:
II
Controller and the LAST
II
Controller to a
Page 4