Worcester Greenstar Heatslave 12/18 Instruction Manual page 33

Floor standing oil fired condensing combination boiler
Hide thumbs Also See for Greenstar Heatslave 12/18:
Table of Contents

Advertisement

8 716 106 252f
30/3/10
12:56
DANFOSS
BFP 11 L3 OIL PUMP
A
B
C
A - Bleed & pressure gauge port
5
L
NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE
USING 28sec KEROSENE:
FUEL
OIL
PUMP
NOZZLE
FLOW RATE
PRESSURE
(p.s.i.)
Kg/h
12/18 - Bentone Sterling 40 Burner:
0.35 80°SR
115
1.04
0.45 80°S
115
1.29
0.50 80°ES
140
1.55
18/25 - Bentone Sterling 50 Burner:
0.50 80°EH
130
1.56
0.55 80°EH
145
1.86
0.65 80°EH
150
2.17
12/18 - Riello RDB 1 Burner :
0.35 80°SR
105
1. 0 4
0.45 60°ES
120
1.29
0.50 60°ES
125
1.55
18/25 - Riello RDB 2.2 Burner
0.50 60°ES
125
1.56
0.65 60°ES
120
1.86
0.75 60°ES
115
2.17
25/32 - Riello RDB 2.2 Burner
0.75 60°ES
105
2.15
0.75 60°ES
140
2.45
0.85 60°ES
150
2.75
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE 12/18-18/25-25/32
8 716 106 252f (03/2010)
Page 33
RIELLO
SUNTEC
RDB OIL PUMP
AS47C OIL PUMP
A
C
B
B - Pressure adjustment
L
APPROX
APPROX.
FLUE
AIR
%CO
AIR
GAS
DAMPER
2
TEMP.
DISC
SETTING
l/h
( °C )
1.32
66
11.5
2.5
N/A
1.63
70
12.0
4.5
N/A
1.96
73
12.5
5.25
N/A
N/A
1.98
72
11.5
4.25
2.36
79
12.0
6.0
N/A
N/A
2.75
82
12.5
8.0
1.32
64
12 .0
4.5
12kW
1.63
67
12.0
3.0
15-18kW
1.96
72
12.5
4.5
15-18kW
:
18-25kW
1.98
75
11.5
2.0
2.36
78
12.0
3.0
18-25kW
2.75
84
12.5
4.5
18-25kW
:
2.72
78
11.5
3.0
N/A
3.10
80
12.0
4.0
N/A
3.48
83
12.5
5.0
N/A
STARTING THE APPLIANCE
C
B
A
C - Vacuum gauge port
5 Switch on the oil supply.
APPLIANCE
INPUT
OUTPUT
kW
Btu/hr
kW
Btu/hr
12.4
42300
12
40900
15.5
52900
15
51200
18.6
63500
18
61400
18.6
63300
18
61400
22.2
75100
21.5
73400
25.8
87900
25
85300
12.4
42300
12
40900
15.5
52900
15
51200
18.6
6 3500
18
61400
18.6
63300
18
61400
22.2
75100
21.5
73400
25.8
8 9700
25
85300
25.5
87040
25
85300
29.1
99200
28.5
97200
32.7
111400
32
109200
Check the CO
levels and adjust the air
2
shutter (L) setting according to the table
opposite.
Check the flue gas temperature is close to
the values shown in the table.
If the flue gas temperature is too high and
the baffles are correctly fitted, then reduce
the oil pump pressure (B) 5-10 p.s.i. to
compensate for nozzle variations.
Turn off the electrical supply.
Isolate the oil supply to the burner.
Remove the oil pressure gauge.
Refit the blanking plug (A).
Check and rectify any oil leaks.
Switch on the electrical supply.
Restart the boiler and run for 5 minutes.
Recheck the CO
levels and if required,
2
adjust the air shutter setting (L) to obtain
the correct CO
level.
2
STARTING THE APPLIANCE
33