In case of heating at the cooling mode or cooling at the heating mode
operate at the operation of
Check the resistance value
apply to the connector of outdoor
fan during the operation of
Samsung Electronics
141 Kinderkamack Rd, Park Ridge, NJ 07656 Tel: 201-782-1782 Fax: 201-782-1783 Web: www.amgair.com Email: info@amgair.com
From the previous page
Does the
EEV operate
normally?
Yes
Does
the outdoor fan
compressor?
No
Is the
outdoor fan connected
correctly?
Yes
of outdoor fan.
OK
Dose the
voltage of DC300V
outdoor unit?
No
Outdoor PCB error
No
Is much frost
in the heat exchanger?
Yes
Check the
resistance value of EEV coil.
OK
Is much frost
in the heat exchanger?
Yes
EEV main body error
Yes
No
NG
Yes
Air Marketing Group LLC
Troubleshooting
(cont.)
No
Connect the connector.
NG
EEV coil error
No
Exchange
the out PCB.
The over shortage of refrigerant, Insufficient
Capacity, Load estimation error
Connect the connector.
Outdoor fan error
Check the motor wire.