Sensor Resistance Values - Honeywell SDC 7-21 Installation Instructions Manual

Heating controller / district heating controller sdc
Hide thumbs Also See for SDC 7-21:
Table of Contents

Advertisement

Technical data
7.2.1
°C
–20
220.6
–18
195.4
–16
173.5
–14
154.2
–12
137.3
–10
122.4
–8
109.2
–6
97.56
–4
87.30
–2
78.23
7.2.2
Ω
°C
0
1000.00
10
1039.02
20
1077.93
25
1093.46
30
1116.72
40
1155.39
50
1193.95
60
1232.39
70
1270.72
75
1289.84
36
7.2

Sensor resistance values

NTC 20
For outside sensor (OT), heat generator sensor (BLRS/BS), tank
sensor (DHWS), mixed heating circuit 1 flow sensor (VF1), mixed
heating circuit 2 flow sensor (VF2), variable input 1 (VI-1) (setting
not for exhaust gas sensor), variable input 2 (VI-2), variable input 3
(VI-3), collector tank/buffer sensor (SBUS).
°C
0
70.20
2
63.04
4
56.69
6
51.05
8
46.03
10
41.56
12
37.55
14
33.97
16
30.77
18
27.90
Pos: 12 / 156 -Hon eywell/ Mont age /Fu ehle r-Wide rsta ndswe rte (2 ) @ 1 \mo d_1 207 651 4386 66_ 6.d oc @ 1 017 9
PT 1000
For variable input 1 (VI-1) (setting of exhaust gas sensor),
collector flow sensor (SPFS).
Ω
°C
80
1308.93
85
1327.99
90
1347.02
95
1366.03
100
1385.00
105
1403.95
110
1422.86
115
1441.75
120
1460.61
130
1498.24
Pos: 13 / 156 -Hon eywell/ Mont age /Fu ehle r-M essb ereic he @ 1\m od_ 120 765 143 2947 _6. doc @ 101 47
°C
20
25.34
25
20.00
30
15.88
35
12.69
40
10.21
45
8.258
50
6.718
55
5.495
60
4.518
65
3.734
Ω
°C
140
1535.75
150
1573.15
160
1610.43
170
1647.60
180
1684.65
190
1721.58
200
1758.40
220
1831.68
240
1904.51
260
1976.86
SDC
°C
70
3.100
75
2.587
80
2.168
85
1.824
90
1.542
95
1.308
100
1.114
Ω
°C
280
2048.76
300
2120.19
320
2191.15
340
2261.66
360
2331.69
380
2401.27
400
2470.38
450
2641.12
500
2811.00
MU1H-0438GE51 R0313

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sdc 12-31Sdc 9-21

Table of Contents