Panasonic WH-MDF09C3E8 Service Manual page 89

Air-to-water heatpump system
Hide thumbs Also See for WH-MDF09C3E8:
Table of Contents

Advertisement

16.5.11 Indoor/Outdoor Abnormal Communication (H90)
Malfunction Decision Conditions:
During operation of heating, the data received from outdoor unit in indoor unit signal transmission is checked
whether it is normal.
Malfunction Caused:
1
Faulty outdoor unit PCB (main).
2
Faulty indoor unit PCB (main).
3
Indoor-outdoor signal transmission error due to wrong wiring.
4
Indoor-outdoor signal transmission error due to breaking of wire in the connection wires between the indoor
and outdoor units.
5
Indoor-outdoor signal transmission error due to disturbed power supply waveform.
Abnormality Judgment:
Continue for 1 minute after operation.