Panasonic WH-MDF09C3E8 Service Manual page 100

Air-to-water heatpump system
Hide thumbs Also See for WH-MDF09C3E8:
Table of Contents

Advertisement

16.5.22 Output Over Current Detection (F23)
Malfunction Decision Conditions:
During operation of heating, when outdoor DC current is above 40.1 ± 5.0A (for: UD07~09CE) OR 44.7 ± 5.0A
(for: UD12~16CE) is detected by the IPM DC Peak sensing circuitry in the outdoor unit PCB (main).
Malfunction Caused:
1
Faulty outdoor unit PCB (main).
2
Faulty compressor.
Abnormality Judgment:
Continue for 7 times.