Panasonic WH-MDF09C3E8 Service Manual page 83

Air-to-water heatpump system
Hide thumbs Also See for WH-MDF09C3E8:
Table of Contents

Advertisement

16.5.5 Water Flow Switch Abnormality (H62)
Malfunction Decision Conditions:
During operation of heating, the water flow detected by the indoor water flow switch is used to determine water
flow error.
Malfunction Caused:
1
Faulty water pump.
2
Water leak in system.
3
Faulty connector connection.
4
Faulty water flow switch.
5
Faulty indoor unit PCB (main).
Abnormality Judgment:
Continue for 10 seconds (but no judgment for 9 minutes after compressor startup/restart).
83

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents