4 | Introduction - LG LS090HSV4 Engineering Manual

Single zone high efficiency wall mount
Hide thumbs Also See for LS090HSV4:
Table of Contents

Advertisement

inSTAllATion & lAyoUT beST PrAcTiceS
Pipe Sleeves at Penetrations
LG requires that all pipe penetrations through walls, floors, and pipes buried underground be properly insulated and routed through an
appropriate wall sleeve of sufficient size to prevent compression of refrigerant pipe insulation and free movement of the pipe within the
sleeve. Underground refrigerant pipe shall be routed inside a protective sleeve to prevent insulation deterioration. Refer to Figure 24.
Figure 24: Pipe Sleeve options.
Diameter of penetrations shall be determined by pipe diameter plus the thickness of the insulation.
Underground refrigerant Piping
Refrigerant pipe installed underground should be routed inside a
vapor tight protective sleeve to prevent insulation deterioration and
water infiltration. Refrigerant pipe installed inside underground
casing must be continuous without any joints. Underground
refrigerant pipe must be located at a level below the frost line.
Table 21: Utility Conduit Sizes.
Liquid Pipe
1
3/8 (1-1/8
1/4 (1.0)
4
3
3/8 (1-1/8)
4
3
oD pipe diameter in inches; Values in parenthesis () indicate oD of pipe with insulation jacket.
1
Diameter of pipe with insulation. Thickness of pipe insulation is typical. Actual required thickness may
2
vary based on surrounding ambient conditions and should be calculated and specified by the design
engineer.
Insulation thickness (value in parenthesis) = 3/8 inch.
3
Insulation thickness (value in parenthesis) = 1 inch.
4
Vapor Pipe
1
)
1/2 (2.0
)
5/8 (2-1/8
2,3
2,4
4
4
4
4
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG " is a registered trademark of LG Corp.
refrigerant Piping System Layout
Figure 25: Typical Arrangement of Refrigerant Pipe and Cable(s) in a
Utility Conduit.
)
2,4
Table 22: Heat Pump Unit Refrigerant Pipe Connections
(All Brazed Type).
Model
LSU090HSV4, LSU120HSV4
LSU180HSV4
Vapor Line
Insulation Material
Liquid Line
Pipe Sleeve
Insulation
Material
Min. 18 Gauge
Power/Communication
Cable
Liquid Conn.
Vapor Conn.
(inches)
(inches)
1/4
3/8
3/8
5/8
reFrIGerant deSIGn | 47

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ls120hsv4Ls180hsv4

Table of Contents