LG LS090HSV4 Engineering Manual page 11

Single zone high efficiency wall mount
Hide thumbs Also See for LS090HSV4:
Table of Contents

Advertisement

Table 2: Single Zone High Efficiency System Specifications.
System Model number (IDU/oDU)
Cooling Capacity (Min/Rated/Max) (Btu/h)
Cooling Power Input
(kW)
1
Heating Capacity (Min/Rated/Max) (Btu/h)
Heating Power Input
(kW)
1
CoP
Maximum Heating Capacity (Btu/h)
outdoor 17 °F (WB)/Indoor 70 °F (DB)
outdoor 5°F (WB)/Indoor 70 °F (DB)
outdoor -4 °F (WB)/Indoor 70 °F (DB)
EER
SEER
HSPF
Power Supply (V/Hz/Ø)
ODU Operating Range
2
Cooling (°F DB)
Heating (°F WB)
IDU Operating Range
Cooling (°F WB)
Heating (°F DB)
Indoor Temperature Setting Range
Cooling (°F)
Heating (°F)
Unit Data
Refrigerant Type
3
Refrigerant Control
IDU Sound Pressure
dB(A) (H/M/L/Sleep)
4
oDU Sound Pressure
dB(A)
4
Unit Weight (lbs)
IDU (net/Shipping)
oDU (net/Shipping)
Power/Communication Cable
5
Compressor
Compressor Type (Qty)
Fan
IDU Type (Qty)
oDU Type (Qty)
Motor/Drive
Airflow Rate
IDU Max/H/M/L (CFM)
oDU Max (CFM)
Piping
Liquid Line (in, oD)
Vapor Line (in, oD)
Condensation Line (oD, ID)
Additional Refrigerant Charge (oz/ft)
Pipe Length
(Minimum/Maximum)(ft)
6
Piping Length
(no add'l refrigerant, ft)
6
Max Elevation Difference (ft)
EEV: Electronic Expansion Valve
IDU: Indoor Unit
Power Input is rated at high speed.
1
optional low Ambient Wind Baffle Kit allows operation down to 0°F in cooling mode.
2
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A
3
refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA.
Sound Pressure levels are tested in an anechoic chamber under ISo Standard 1996.
4
All power wiring/communication cables are field supplied and are to be minimum 18 AWG, 4-conductor,
5
stranded, shielded and must comply with applicable local and national codes.
LS090HSV4
(LSn090HSV4/LSU090HSV4)
1,023 ~ 9,000 ~ 12,625
0.68
1,023 ~ 10,800 ~ 17,061
0.70
4.51
8,856 (82%)
7,452 (69%)
7,236 (67%)
13.3
21.5
10.8
38/33/23/19
20/26
75/79
(no. x AWG)
Single Rotary (1)
423/353/272/191
1,165
1/4
3/8
27/32, 5/8
0.22
6.6/65.6
41.0
32.8
oDU: outdoor Unit
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG " is a registered trademark of LG Corp.
LS120HSV4
(LSn120HSV4/LSU120HSV4)
1,023 ~ 11,200 ~ 13,785
1,023 ~ 13,300 ~ 22,178
10,906 (82%)
9,177 (69%)
8,911 (67%)
208-230/60/1
14 to 118
-4 to +65
53 to 75
60 to 86
64 to 86
60 to 86
39/33/23/19
45
Single Rotary (1)
Cross Flow (1)
Propeller (1)
Brushless Digitally Controlled/Direct
423/353/272/191
27/32, 5/8
6.6/65.6
Piping lengths are equivalent.
6
This unit comes with a dry helium charge.
This data is rated 0 ft above sea level with 24.6 of refrigerant line per indoor unit and a 0 ft level
difference outdoor and indoor units.
Cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF wet
bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 59ºF wet
bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
generAl DATA
LS180HSV4
(LSn180HSV4/LSU180HSV4)
3,070~18,200~29,515
0.90
3,070 ~ 22,000 ~ 38,898
1.0
3.90
18,040 (82%)
15,180 (69%)
14,740 (67%)
12.5
21.5
11.0
R410A
EEV
45/40/35/29
45
20/26
75/79
4 x 18
Twin Rotary (1)
735/622/509/399
1,165
1/4
3/8
0.22
41.0
32.8
Product data | 11
1.45
1.76
3.66
12.6
20.5
9.7
53
31/36
121/131
2,119
3/8
5/8
27/32, 5/8
0.38
9.84/98.4
24.6
49.2