AcceSSorieS
lg Monitoring View (lgMV) Diagnostic Software and cable
(PRCTSL1 and PRCTFE1)
LGMV software allows the service technician or commissioning agent to connect a computer
USB port to the outdoor unit main printed circuit board (PCB) using an accessory cable
without the need for a separate interface device. The main screen for LGMV shall allow user
to view the following real time data on one screen:
• Actual inverter compressor speed
• Target inverter compressor speed
• Actual outdoor fan speed
• Target outdoor unit fan speed
• Actual superheat
• Inverter compressor current value
• outdoor air temperature
• Actual high pressure/saturation temperature
• Actual low pressure/saturation temperature
• Suction temperature
• Inverter compressor discharge temperature
• outdoor coil pipe temperature
• Liquid line pipe temperature
• Inverter compressor operation indicator
light
• Four-way reversing valve operation
Additional screens can be accessed by tabs on the main screen:
1. Cycleview: Graphic of internal components including:
• Compressors showing actual speeds
• EEVs
• IDUs
• Low and high pressures
2. Setting: Converts metric values to imperial values.
3. Making Data: Recording of real time data to a separate file created to be stored on the
user's computer.
4. Loading Data: Recorded data from a saved ".CSV" file can be loaded to create an LGMV
session.
5. Electrical Data: The lower half of main screen is changed to show the following:
• Inverter compressor
- Amps
- Volts
The software is available in a high version with all of the features listed above. The low version has all features as the high version without
Target High Pressure and Target Low Pressure values shown on main screen.
In lieu of connecting to the oDU, user has the option to connect to IDU with the use of a USB to RS-485 connector kit. When connected
through IDU, user will not be able to record data.
This software can be used to both commission new systems and troubleshoot existing systems. LGMV data can be recorded to a ".CSV" file
and emailed to an LG representative to assist with diagnostic evaluations.
Recommended Minimum PC Configuration:
• CPU: Pentium
IV 1.6 GHz
®
• operating System: Windows
XP/Vista
28 | Product data
indicator light
• Pressure graph showing actual low pres-
sure and actual high pressure levels
• Error code display
• operating mode indicator
• Total number of connected indoor units (for
multi zone systems)
• Communication indicator lights
• Unit error code
• Indoor unit capacity
• Indoor unit operating mode
• Indoor unit fan speed
• Indoor unit room temperature
• Indoor unit inlet pipe temperature
• Indoor unit outlet pipe temperature
• Temperature and pressure sensors
• Four-way reversing valve
• outdoor fans showing status and speeds
-
Power Hz
- Inverter control board fan Hz
• Main Memory: 256 MB
nT/2000/
• Hard Disk: 600 MB when operating
®
• Web Browser: Internet Explorer