74 ALTERNATING 'L' AND '6' - FALSE FLAME LOCKOUT
Restart the boiler, does Boiler Work OK?
Separate the flame detection electrode in-line
connector. Is there continuity between the terminals
pins connected to the electrode?
Re St ARt PRo Ced URe - To restart boiler, turn mode knob to restart position and immediately turn knob back to required setting.
75 ALTERNATING 'F' AND '1' - LOW WATER PRESSURE
Are the Boiler and CH System filled with water and
all isolation and radiator valves open (check pressure
gauge is between 1 to 1.5 bar)?
Are connections on water pressure sensor secure?
76 ALTERNATING 'F' AND '2' - FLAME LOSS
Does the boiler ignite for a short
time and then extinguish?
YES
Check the detection electrode and
associated harness for: continuity,
visual condition and position (Refer
to Frame 49). Check if condensate
pipe is blocked. Check if flue is
blocked.
Replace as necessary
* n ote: due to the wave form of the rectified
voltage, the reading will vary depending on
the type of meter used to measure the value.
In general terms a reading greater than 150V
indicates that the correct voltage is supplied
to the gas valve.
56
fAUlt
NO
YES
NO
Is the Gas Pressure available at
the Boiler Inlet (18 mbar)?
Is 215Vdc supply available at the
Gas Valve while the flame is on?
(* See note)
Check spark generator and
associated harness for: continuity
and visual condition. (Refer to Frame
48) Are these functioning correctly?
Check ignition electrode and
associated harness for: continuity,
visual condition and position.
(Refer to Frame 54) Are these
functioning correctly?
Check siphon and condensate drain
pipe work for blockage and rectify if
necessary. Boiler now working OK?
f indinG
Check routing and integrity of internal boiler
YES
wiring is OK. Check condition of Flame Sense
Electrode and replace if deteriorated.
YES
Replace Flame Detection Electrode
NO
Check routing and integrity of internal boiler wiring
NO
Fill and vent the system and open all isolation valves
Re-fit connections
NO
Replace water pressure sensor
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
Logic Combi ES -
Check gas supply and
rectify fault
Check wiring from gas
valve to PCB for continuity.
If the wiring is OK then
replace the PCB
Replace Spark Generator
and Harness as necessary.
Replace Ignition
Electrode and
associated harness as
necessary
Replace Gas Valve
Installation and Servicing