Drain Installation - Ultra-Aire XT205H Installation Instructions Manual

Table of Contents

Advertisement

The Ultra-Aire XT205H generates condensate.
Place a secondary drain pan under the dehumidifier if it is suspended above a finished area or above an area
where water leakage could cause damage.
A drain trap is required for the dehumidifier to drain properly. Install a 3/4" threaded male NPT adapter to the
drain pan. Install a drain pipe assembly utilizing 3/4" PVC pipe to transport the condensate to a drain. Pitch
of drain should be 1" per 10'.
An optional condensate pump kit is available for use with the Ultra-Aire XT205H and may be installed if lift is
Drain Port
required to dispose of condensate. Condensate is automatically pumped to a remote location when the
water level in the pump's reservoir rises to close the float switch.
The pump also contains a safety float switch. The white leads from this switch extend from beneath the
pump cover. This switch should be installed in series with the field wire that connects to the common lead
from the Ultra-Aire XT205H to the control panel. If the pump fails, this switch opens the common control
circuit and stops water production before the reservoir overflows. Contact a qualified electrician to install the
safety float switch to the Ultra-Aire XT205H dehumidifier.
Note: An optional condensate pump kit and an automatic cut-off device can be purchased through your
dealer or online.

Drain Installation

Drain Trap
www.Ultra-Aire.com | 1-800-533-7533
Drain
Trap
Drain Port
Secondary Drain Pan
DRAIN INSTALLATION
Drain Port
Drain Trap
Ultra-Aire XT205H Installation Instructions
Drain
Trap
Drain Port
Secondary Dra
9