ULTRA AIRE XT105H / XT155H / XT205H Installation & Operation Instructions The Ultra Aire XT Dehumidifiers are ventilating Serial Number dehumidifiers that integrate into the heating and Install Date cooling system to provide the ultimate in comfort, Sold By health and property protection through:...
CONCERNING THE USE OF THE APPLIANCE BY A PERSON RESPONSIBLE FOR THEIR SAFETY. CHILDREN SHOULD BE SUPERVISED TO ENSURE THAT THEY DO NOT PLAY WITH THE APPLIANCE. Ultra-Aire.com | (800) 533-7533 Ultra Aire XT105H / XT155H / XT205H Installation Instructions...
Adhere seal onto the back of the oval duct and mount the duct to the front of the dehumidifier using the screws provided. 6" Fresh Air Inlet (Optional) 10" Return Air Inlet 10" Supply Air Outlet Collars and hardware are SIDE VIEW FRONT VIEW located here. Ultra-Aire.com | (800) 533-7533 Ultra Aire XT105H / XT155H / XT205H Installation Instructions...
• Be sure to consult the electrical schematic in the CONTROLS Section (page 12) of this manual or inside the access panel of the Ultra Aire Dehumidifier before making control connections. Ultra Aire XT105H / XT155H / XT205H Installation Instructions Ultra-Aire.com | (800) 533-7533...
Note: An optional condensate pump kit and an automatic cut-off device can be purchased through your dealer or online. Drain Installation Drain Port Drain Trap Drain Port Secondary Drain Pan Drain Trap Drain Port Secondary Drain Drain Trap Ultra-Aire.com | (800) 533-7533 Ultra Aire XT105H / XT155H / XT205H Installation Instructions...
Proper air distribution is important to ensure even humidity control and heat distribution throughout the structure. • DO NOT locate the return in a bathroom or a kitchen. Ultra Aire XT105H / XT155H / XT205H Installation Instructions Ultra-Aire.com | (800) 533-7533...
• DO NOT locate return in a bathroom or kitchen. • Control should be located remotely from the dehumidifier and placed in a central location. Please visit our website at www.ultra-aire.com/install-options/ for more installation options. Dedicated Ultra Aire Return to HVAC Supply...
• An insulated 6" diameter duct on the XT155H and XT205H provides up to 100 CFM of outside air. • An insulated 6” diameter duct on the XT105H provides up to 75 CFM of outside air. • If a motorized damper is not being used, fresh air is controlled by the manual damper in the 6" collar of the Ultra Aire Dehumidifier.
Make contact between 24V and FAN terminals Power HVAC Accessory Connect the accessory to the COM and 24V terminals NOTE: 18 gauge wire needed between the Ultra Aire Dehumidifier and the external control. Ultra Aire XT105H / XT155H / XT205H Installation Instructions Ultra-Aire.com | (800) 533-7533...
Side View Front View Front View Step 3: Close the filter door by swinging it shut and reattaching the latch. Filter Door Open Filter Door Closed Side View Ultra-Aire.com | (800) 533-7533 Ultra Aire XT105H / XT155H / XT205H Installation Instructions...
9. If this test works, then the field control wiring flow restricted. is ok. 6. Defective fan or relay. 10. If the problem persists, then the control is most likely faulty. Ultra-Aire.com | (800) 533-7533 Ultra Aire XT105H / XT155H / XT205H Installation Instructions...
Page 16
If any of the old charge is left in the system, it must be recovered before weighing in the new charge. Refer to the unit nameplate for the correct charge weight and refrigerant type. Ultra Aire XT105H / XT155H / XT205H Installation Instructions Ultra-Aire.com | (800) 533-7533...