 Mount chamber lid
and air filter
(accessory).
In case of bottom suction.
(1)Remove the chamber lid. (7 locations)
(2)Reattach the removed chamber lid in the
orientation shown in Fig.(7 locations)
(3)Attach sealing pad as shown in the figure
below. (Stored in outlet vent) (only for 50-60
type)
(In order to take in the air inside the ceiling,
and when not taking in air from outdoor air, it
is not necessary to stick.)
• Attach the sealing pad (accessory)
to the plate metal sections which
are not covered by anti-sweat
material.
• Make sure there are no gaps
between the different pieces of
sealing pad.
(4)Attach the hanger (right) insulation to the right hanger. (Stored in outlet vent)
(See the below figure for the sticking base line.)
(5)Attach the air filter (accessory) in the manner shown in the diagram.
In case of bottom side
English
(1)
Air discharge
Sealing pad (Small)
(3)
(accessory)
Air inlet
Air
Sealing pad (Large)
discharge
(accessory)
Anti-sweat material
included with the product
For rear intake type
Hanger bracket (right)
Hanger (right) insulation
Slit
Attach the
Main unit
filter to the
main unit
while
pushing
down on the
Force
bends.
(2 bends for
25-35 type,
Filter
3 bends for
Force
50-60 type)
(2)
Air inlet
Chamber lid
Air discharge
Sealing pad (Small)
(accessory)
Air inlet
Air
discharge
Anti-sweat material
included with the product
For bottom intake type
ARROW VIEW
In case of back side
Chamber lid
Air inlet
Sealing pad (Large)
(accessory)
4