Daikin FXLQ-P Technical Data Manual page 6

Floor standing unit
Hide thumbs Also See for FXLQ-P:
Table of Contents

Advertisement

2
Specifications
Notes
(1) Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal)
(2) Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal)
(3) Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
(4) Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
(5) Maximum allowable voltage range variation between phases is 2%.
2
(6) MCA/MFA: MCA = 1.25 x FLA
(7) MFA ≤ 4 x FLA
(8) Next lower standard fuse rating minimum 15A
(9) Select wire size based on the value of MCA
(10) Instead of a fuse, use a circuit breaker
4
• Indoor Unit • FXLQ-P
• VRV Systems • FXLQ-P