Capacity Correction Factor - Daikin FXLQ-P Technical Data Manual

Floor standing unit
Hide thumbs Also See for FXLQ-P:
Table of Contents

Advertisement

5
Capacity tables

5 - 3 Capacity Correction Factor

FXLQ-P
Indoor air
temperature
TC
FXLQ20
SHF
TC
FXLQ25
SHF
TC
FXLQ32
SHF
TC
FXLQ40
SHF
TC
FXLQ50
SHF
TC
FXLQ63
SHF
How to use this table:
Capacity: Total capacity for High sensible mode = Total capacity for normal capacity table X TC ratio.
SHF: SHF for High sensible mode = SHF for normal capacity table X SHF ratio.
In case of SHF is bigger than 1, SHF is "1"
When selecting units for mixed (RA DX indoor units + VRV DX indoor unit),
Correction C
corresponds with Te = 9°C TC ratio value for each type of Indoor unit,
i
depending on indoor ambient design temperature X/Y °CDB/°CWB
Correction C
corresponds with Te = 9°C TC ratio value for each type of indoor unit,
t
depending on indoor ambient temperature 29/19 °CDB/°CWB
So verwenden Sie diese Tabelle:
Leistung:Gesamtleistung (GL) für hochfühlbaren Leistungsmodus = Gesamtleistung für normale
Leistungstabelle x GL-Verhältnis.
SHF: SHF für hochfühlbaren Leistungsmodus = SHF für normale Leistungstabelle x SHF-Verhältnis.
Für den Fall, dass SHF größer als 1 ist, wird SHF als "1" angenommen.
Bei Auswahl gemischter Geräte (RA DX-Innengerät + VRV DX-Innengerät),
Korrektur C
entspricht dem GL-Verhältniswert für Te = 9 °C für jeden Innengerätetyp, in
i
Abhängigkeit von der Innen-Entwurfstemperatur X/Y °C TK/°C FK
Korrektur C
entspricht dem GL-Verhältniswert für Te = 9 °C für jeden Innengerätetyp, in
t
Abhängigkeit von der Innentemperatur 29/19 °C TK/°C FK
i
t
Cómo utilizar esta tabla:
Capacidad: capacidad total para el modo sensible alto = capacidad total para relación TC de tabla X
de capacidad normal.
SHF: SHF para modo sensible alto = SHF para relación SHF de tabla X de capacidad normal.
En caso de que SHF sea superior a 1, SHF es "1"
Si se seleccionan unidades combinadas (Unidades interiores DX RA + unidades interiores DX VRV),
La corrección C
corresponde a Te = 9°C valor de relación TC para cada tipo de unidad
i
interior, en función de la temperatura de diseño ambiente interior X/Y °CBS/°CBH
La corrección C
corresponde a Te = 9°C valor de relación TC para cada tipo de unidad
t
interior, en función de la temperatura ambiente interior 29/19 °CBS/°CBH
Comment utiliser ce tableau :
Puissance :Puissance totale pour le mode haute sensibilité = Puissance totale indiquée dans le
tableau de puissance normale X rapport PT.
FCS : FCS pour le mode haute sensibilité =
FCS indiqué dans le tableau de puissance normale X rapport FCS.
Si le FCS est supérieur à 1, le FCS correspond à « 1 »
Lors de la sélection d'unités pour une installation mixte (unités intérieures DX RA + unité intérieure DX VRV),
La correction C
correspond à Te = 9 °C / valeur de rapport PT pour chaque type d'unité
i
intérieure, pour une température ambiante intérieure de calcul de X/Y °CBS/°CBH
La correction C
correspond à Te = 9 °C / valeur de rapport PT pour chaque type d'unité
t
intérieure, pour une température ambiante intérieure de 29/19 °CBS/°CBH
• Indoor Unit • FXLQ-P
14.0 °CWB
16.0 °CWB
20.0 °CDB
23.0 °CDB
0.650
0.709
1.205
1.160
0.650
0.711
1.206
1.158
0.647
0.709
1.212
1.160
0.661
0.714
1.184
1.154
0.654
0.709
1.194
1.160
0.662
0.713
1.179
1.155
• VRV Systems • FXLQ-P
Capacity correction factor Te = 9°C
18.0 °CWB
19.0 °CWB
20.0 °CWB
26.0 °CDB
27.0 °CDB
28.0 °CDB
0.767
0.788
0.808
1.108
1.090
1.073
0.769
0.791
0.812
1.108
1.088
1.071
0.767
0.787
0.807
1.109
1.090
1.073
0.775
0.797
0.814
1.103
1.084
1.071
0.768
0.790
0.809
1.107
1.088
1.073
0.773
0.795
0.813
1.103
1.084
1.071
Come utilizzare questa tabella
Capacità: Capacità totale per modalità ad alta capacità sensibile = Capacità totale per tabella
capacità normali X rapporto TC.
SHF: SHF per modalità ad alta capacità sensibile = SHF per tabella capacità normali X rapporto SHF.
Qualora il valore SHF sia maggiore di 1, SHF è "1"
Quando si selezionano unità combinate (unità interna ad espansione diretta RA+ unità interna ad
espansione diretta VRV ),
La correzione C
corrisponde a Te = 9°C valore rapporto TC per ogni tipo di unità interna, in
i
base alla temperatura interna di progetto X/Y °CBS/°CBU
La Correzione C
corrisponde a Te = 9°C valore rapporto TC per ogni tipo di unità interna, in
t
base alla temperatura interna di progetto 29/19 °CBS/°CBU
Hoe deze tabel gebruiken:
Vermogen: totaal vermogen voor High Sensible-modus = totaal vermogen voor tabel normaal
vermogen x ratio TV.
SHF: SHF voor High Sensible-modus = SHF voor tabel normaal vermogen x ratio SHF.
Indien SHF groter is dan 1, is SHF "1"
Bij het selecteren van units voor gemengd gebruik (RA DX-binnenunits + VRV DX-binnenunits),
Correctie C
komt overeen met ratiowaarde Te = 9°C TC voor elk type binnenunit, afhankelijk
i
van de ontwerptemperatuur van de binnenunit X/Y °CDB/°CNB
Correctie C
komt overeen met ratiowaarde Te = 9°C TC voor elk type binnenunit, afhankelijk
t
van de omgevingstemperatuur van de binnenunit 29/19 °CDB/°CNB
VRV DX):
i
t
Kapasite: Yüksek hassasiyet modu toplam kapasitesi = Normal kapasite tablosu için toplam kapasite
SHF, 1'den büyük ise SHF "1"dir
C
i
C
t
22.0 °CWB
24.0 °CWB
30.0 °CDB
32.0 °CDB
0.842
0.866
1.046
1.029
0.844
0.867
1.046
1.029
0.842
0.866
1.045
1.028
0.844
0.867
1.047
1.036
0.842
0.865
1.046
1.029
0.843
0.866
1.049
1.039