Air conditioner operating conditions

For proper performance, operate the air conditioner under the following temperature conditions:
Cooling operation
Dry bulb temp.
Heating operation
Wet bulb temp.
If air conditioner is used outside of the above conditions, safety protection may work.
13

Functions to be implemented locally

Handling existing pipe
When using the existing pipe, carefully check for the following:
• Wall thickness (within the specifi ed range)
• Scratches and dents
• Water, oil, dirt, or dust in the pipe
• Flare looseness and leakage from welds
• Deterioration of copper pipe and heat insulator
Cautions for using existing pipe
• Do not reuse a fl are nut to prevent gas leaks.
Replace it with the supplied fl are nut and then process it to a fl are.
• Blow nitrogen gas or use an appropriate means to keep the inside of the pipe clean. If discolored oil or much
residue is discharged, wash the pipe.
• Check welds, if any, on the pipe for gas leaks.
When the pipe corresponds to any of the following, do not use it. Install a new pipe instead.
• The pipe has been opened (disconnected from indoor unit or outdoor unit) for a long period.
• The pipe has been connected to an outdoor unit that does not use refrigerant R22, R410A or R407C.
• The existing pipe must have a wall thickness equal to or larger than the following thicknesses.
Reference outside
Wall thickness (mm)
diameter (mm)
Ø6.4
0.8
Ø9.5
0.8
Ø12.7
0.8
• Do not use any pipe with a wall thickness less than these thicknesses due to insuffi cient pressure capacity.
25-EN
–10 °C to 46 °C
–15 °C to 24 °C
– 13 –
14

Appendix

Work instructions
The existing R22 and R407C piping can be reused for
our digital inverter R410A product installations.
WARNING
Confirming the existence of scratches or dents on
the existing pipes and confirming the reliability of
the pipe strength are conventionally referred to the
local site.
If the specified conditions can be cleared, it is
possible to update existing R22 and R407C pipes
to those for R410A models.
Basic conditions needed to reuse existing
pipes
Check and observe the presence of three conditions in
the refrigerant piping works.
1. Dry (There is no moisture inside of the pipes.)
2. Clean (There is no dust inside of the pipes.)
3. Tight (There are no refrigerant leaks.)
Restrictions for use of existing pipes
In the following cases, the existing pipes should
not be reused as they are. Clean the existing pipes
or exchange them with new pipes.
1. When a scratch or dent is heavy, be sure to use new
pipes for the refrigerant piping works.
2. When the existing pipe thickness is thinner than the
specified "Pipe diameter and thickness," be sure to
use new pipes for the refrigerant piping works.
• The operating pressure of R410A is high (1.6
times that of R22 and R407C). If there is a scratch
or dent on the pipe or a thinner pipe is used, the
pressure strength may be inadequate, which may
cause the pipe to break in the worst case.
* Pipe diameter and thickness (mm)
Pipe outer diameter
Ø6.4
R410A
Thickness
0.8
R22
(R407C)
• In case the pipe diameter is Ø12.7 mm or less and
the thickness is less than 0.7 mm, be sure to use
new pipes for the refrigerant piping works.
3. When the outdoor unit was left with the pipes
disconnected, or the gas leaked from the pipes and
the pipes were not repaired and refilled.
• There is the possibility of rain water or air,
including moisture, entering the pipe.
4. When refrigerant cannot be recovered using a
refrigerant recovery unit.
• There is the possibility that a large quantity of dirty
oil or moisture remains inside the pipes.
5. When a commercially available dryer is attached to
the existing pipes.
• There is the possibility that copper green rust has
been generated.
6. When the existing air conditioner is removed after
refrigerant has been recovered.
Check if the oil is judged to be clearly different from
normal oil.
• The refrigerator oil is copper rust green in color:
There is the possibility that moisture has mixed
with the oil and rust has been generated inside the
pipe.
• There is discolored oil, a large quantity of residue,
or a bad smell.
• A large quantity of shiny metal dust or other wear
residue can be seen in the refrigerant oil.
7. When the air conditioner has a history of the
compressor failing and being replaced.
• When discolored oil, a large quantity of residue,
shiny metal dust, or other wear residue or mixture
of foreign matter is observed, trouble will occur.
8. When temporary installation and removal of the air
conditioner are repeated such as when leased etc.
9. If the type of refrigerator oil of the existing air
conditioner is other than the following oil (Mineral
oil), Suniso, Freol-S, MS (Synthetic oil), alkyl
benzene (HAB, Barrel-freeze), ester series, PVE
only of ether series.
• The winding-insulation of the compressor may
deteriorate.
NOTE
The above descriptions are results have been confirmed
by our company and represent our views on our air
conditioners, but do not guarantee the use of the existing
pipes of air conditioners that have adopted R410A in
other companies.
Curing of pipes
Ø9.5
Ø12.7
When removing and opening the indoor or outdoor unit
for a long time, cure the pipes as follows:
0.8
0.8
• Otherwise rust may be generated when moisture or
foreign matter due to condensation enters the pipes.
• The rust cannot be removed by cleaning, and new
pipes are necessary.
Placement
Term
location
1 month or more
Outdoors
Less than 1 month
Indoors
Every time
Curing manner
Pinching
Pinching or taping
26-EN