Baxi Platinum 2 Combi 28 GA Installation & Servicing Instructions Manual page 23

Gas fired wall mounted condensing combination boiler
Table of Contents

Advertisement

Wall Thickness
(X)
Fig. 25
Fig. 27
'TOP' Label
© Baxi Heating UK Ltd 2011
Terminal Assembly
Connection Assembly
Fig. 24
(X)
'Peak' to be uppermost
Fig. 26
'TOP' Label
Sealing Tape
9.0 Installation
9.6
HORIZONTAL TELESCOPIC FLUE
1. There are two telescopic sections, the Terminal
Assembly and the Connection Assembly, a roll of sealing
tape and two self tapping screws. A 93° elbow is also
supplied. The outer duct of the Connection Assembly is
painted white. On the Terminal Assembly the outer duct is
unpainted.
2. The two sections can be adjusted to provide a length
between 315mm and 500mm (Fig. 24) when measured
from the flue elbow (there is 50mm engagement into the
elbow).
3. Locate the flue elbow on the adaptor at the top of the
boiler. Set the elbow to the required orientation (Fig. 25).
NOTE: The flue elbow is angled at 93 degrees to
ensure a fall back to the boiler.
4. Measure the distance from the outside wall face to the
elbow. This dimension will be known as 'X' (Fig. 25).
5. If the distance from the flue elbow to the outside face of
the wall ('X' in Fig. 25) is less than 250mm the Connection
Assembly can be discarded and the Terminal Assembly
fitted directly into the elbow.
6. In instances where the dimension 'X' (Fig. 25) is between
Wall
250mm and 315mm it will be necessary to shorten the
Thickness
Terminal Assembly by careful cutting to accommodate
walls of these thicknesses.
7. To dimension 'X' add 50mm. This dimension to be
known as 'Y'.
8. Adjust the two telescopic sections to dimension 'Y' and
seal the joint with the tape provided (Fig. 27). Ensure that
the labels marked 'TOP' on the Terminal and Connection
Assemblies are uppermost.
9. Using the clearance holes in the Connection Assembly
secure it to the Terminal Assembly using the screws
supplied (Fig. 28).
Fig. 28
Fitting The Flue
Securing Screw
23