Capacity Tables - Daikin RKS50BVMB9 Technical Data Manual

Hide thumbs Also See for RKS50BVMB9:
Table of Contents

Advertisement

3

Capacity tables

1
RKS+FTKS50B
3
Cooling capacity
Indoor
EWB
EDB
(°C)
(°C)
TC
14.0
20
5.06
16.0
22
5.22
18.0
25
5.37
19.0
27
5.45
22.0
30
5.68
24.0
32
5.84
RKS+FTKS60B
Cooling capacity
Indoor
EWB
EDB
(°C)
(°C)
TC
14.0
20
6.06
16.0
22
6.22
18.0
25
6.37
19.0
27
6.45
22.0
30
6.68
24.0
32
6.84
RKS+FTKS71B
Cooling capacity
Indoor
EWB
EDB
(°C)
(°C)
TC
14.0
20
7.16
16.0
22
7.32
18.0
25
7.47
19.0
27
7.55
22.0
30
7.78
24.0
32
7.94
RKS+FVKS50B
Cooling capacity
Indoor
EWB
EDB
(°C)
(°C)
TC
14.0
20
4.86
16.0
22
5.02
18.0
25
5.17
19.0
27
5.25
22.0
30
5.48
24.0
32
5.64
SYMBOLS
AFR:
Air flow rate
BF:
Bypass factor
EWB:
Entering wet bulb temp.
EDB:
Entering dry bulb temp.
TC:
Total capacity
SHC:
Sensible heating capacity
PI:
Power input
6
• Pair Application, Inverter Controlled Unit • R-410A • RKS50-60-71BVMB9
20
25
SHC
PI
TC
SHC
PI
3.28
1.31
4.91
3.21
1.41
3.31
1.34
5.07
3.24
1.43
3.34
1.36
5.22
3.27
1.46
3.36
1.38
5.30
3.29
1.47
3.41
1.41
5.53
3.34
1.51
3.45
1.44
5.69
3.38
1.54
20
25
SHC
PI
TC
SHC
PI
3.97
1.77
5.91
3.90
1.87
4.00
1.80
6.07
3.93
1.89
4.03
1.82
6.22
3.96
1.92
4.05
1.84
6.30
3.98
1.93
4.10
1.87
6.53
4.03
1.97
4.14
1.90
6.69
4.07
2.00
20
25
SHC
PI
TC
SHC
PI
4.60
2.18
7.01
4.53
2.28
4.63
2.21
7.17
4.56
2.30
4.67
2.23
7.32
4.60
2.33
4.68
2.25
7.40
4.61
2.34
4.73
2.28
7.63
4.66
2.38
4.77
2.31
7.79
4.70
2.41
20
25
SHC
PI
TC
SHC
PI
3.15
1.35
4.71
3.08
1.45
3.18
1.38
4.87
3.11
1.47
3.22
1.40
5.02
3.15
1.50
3.23
1.42
5.10
3.16
1.51
3.29
1.45
5.33
3.22
1.55
3.32
1.48
5.49
3.25
1.58
• Split - Sky Air • Outdoor Units
230V [50Hz]
Outdoor temperature (°C)
30
TC
SHC
PI
TC
4.76
3.14
1.50
4.70
4.92
3.17
1.53
4.86
5.07
3.20
1.55
5.01
5.15
3.22
1.57
5.09
5.38
3.27
1.60
5.32
5.54
3.31
1.63
5.48
230V [50Hz]
Outdoor temperature (°C)
30
TC
SHC
PI
TC
5.76
3.83
1.96
5.70
5.92
3.86
1.99
5.86
6.07
3.89
2.01
6.01
6.15
3.91
2.03
6.09
6.38
3.96
2.06
6.32
6.54
4.00
2.09
6.48
230V [50Hz]
Outdoor temperature (°C)
30
TC
SHC
PI
TC
6.86
4.46
2.37
6.80
7.02
4.49
2.40
6.96
7.17
4.53
2.42
7.11
7.25
4.54
2.44
7.19
7.48
4.59
2.47
7.42
7.64
4.63
2.50
7.58
230V [50Hz]
Outdoor temperature (°C)
30
TC
SHC
PI
TC
4.56
3.01
1.54
4.50
4.72
3.04
1.57
4.66
4.87
3.08
1.59
4.81
4.95
3.09
1.61
4.89
5.18
3.15
1.64
5.12
5.34
3.18
1.67
5.28
NOTES
3
1. Ratings shown are net capacities which include a deduction for indoor fan
(m
/min)
motor heat
(°CWB)
2.
Shows nominal cooling capacities and power input
(°CDB)
3. TC, PI and SHC must be calculated by interpolation using the figures in the
(kW)
above tables. (Figures out of the tables should not be used for calculation.)
(kW)
4. SHC is based on each EWB and EDB
(kW)
SHC* = SHC correction for other dry bulb
SHC* = 0.02 x AFR (m
Add SHC* to SHC.
5. Capacities are based on following conditions:
Corresponding refrigerant piping length:
Level difference:
6. Air flow rate (AFR) and Bypass factor (BF) are taburated above.
32
35
SHC
PI
TC
SHC
PI
3.11
1.54
4.61
3.07
1.60
3.14
1.56
4.77
3.10
1.62
3.18
1.59
4.92
3.13
1.65
3.19
1.60
5.00
3.15
1.66
3.24
1.64
5.23
3.20
1.70
3.28
1.67
5.39
3.24
1.73
32
35
SHC
PI
TC
SHC
PI
3.80
2.00
5.61
3.76
2.06
3.83
2.02
5.77
3.79
2.08
3.87
2.05
5.92
3.82
2.11
3.88
2.06
6.00
3.84
2.12
3.93
2.10
6.23
3.89
2.16
3.97
2.13
6.39
3.93
2.19
32
35
SHC
PI
TC
SHC
PI
4.43
2.41
6.71
4.39
2.47
4.46
2.43
6.87
4.42
2.49
4.50
2.46
7.02
4.46
2.52
4.52
2.47
7.10
4.47
2.53
4.57
2.51
7.33
4.52
2.57
4.60
2.54
7.49
4.56
2.60
32
35
SHC
PI
TC
SHC
PI
2.98
1.58
4.41
2.94
1.64
3.02
1.60
4.57
2.97
1.66
3.05
1.63
4.72
3.01
1.69
3.07
1.64
4.80
3.02
1.70
3.12
1.68
5.03
3.08
1.74
3.15
1.71
5.19
3.11
1.77
3
/min) x (1-BF) x (DB-EDB)
AFR
11.4
BF
0.22
40
TC
SHC
PI
4.46
3.00
1.69
4.62
3.03
1.72
4.77
3.06
1.74
4.85
3.08
1.76
5.08
3.13
1.79
5.24
3.17
1.82
3D040892
AFR
16.2
BF
0.29
40
TC
SHC
PI
5.46
3.69
2.15
5.62
3.72
2.18
5.77
3.75
2.20
5.85
3.77
2.22
6.08
3.82
2.25
6.24
3.86
2.28
3D04089
AFR
16.7
BF
0.27
40
TC
SHC
PI
6.56
4.32
2.56
6.72
4.35
2.59
6.87
4.39
2.61
6.95
4.40
2.63
7.18
4.45
2.66
7.34
4.49
2.69
3D040896
AFR
10.8
BF
0.23
40
TC
SHC
PI
4.26
2.87
1.73
4.42
2.90
1.76
4.57
2.94
1.78
4.65
2.95
1.80
4.88
3.01
1.83
5.04
3.04
1.86
3D040894
7.5 m
0 m

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rks60bvmb9Rks71bvmb9