Wiring
WARNING
1) Do not use tapped wires, stand wires, extensioncords, or starbust connections, as they may cause overheating, electrical shock, or fire.
2) Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the
terminal block.) Doing so may cause electric shock or fire.
3) Be sure to install an earth leak detector. (One that can handle higher harmonics.)
(This unit uses an inverter, which means that it must be used an earth leak detector capable handling harmonics in order to
prevent malfunctioning of the earth leak detector itself.)
4) Use an all-pole disconnection type breaker with at least 3 mm between the contact point gaps.
• Do not turn ON the safety breaker until all work is completed.
1) Strip the insulation from the wire (20mm).
2) Connect the connection wires between the
indoor and outdoor units so that the terminal
numbers match. Tighten the terminal screws
securely. We recommend a flathead screw-
driver be used to tighten the screws. The
screws are packed with the terminal board.
CAUTION
When connecting the connection wires to the
terminal board using a single core wire, be sure
to perform curling.
Problems with the work may cause heat and fires.
• Ground terminal installation
Use the following method when installing the round
crimp-style terminal.
Screw
Round crimp-
style terminal
Flat washer
Good
3) Pull the wire and make sure that it does not disconnect. Then fix the wire in place with a wire stop.
■ Earth
This air conditioner must be earthed.
For earthing, follow the applicable local standard for electrical installations.
■English
Indoor unit
Shape the wires so that
there is no lifting of the
service hatch or other
structural parts.
Screw
Flat washer
Round crimp-
style terminal
Wrong
Room
Room
A
B
Room
Room
C
D
To room D
To room C
H05VV
Room A
To room B
Secure the branch wiring firmly using the 4
included screws, as shown in the figure.
Secure firmly, making sure no outside pressure is
exerted on the terminals.
Outdoor unit
Be sure to use the dedicated circuits.
50Hz
Earth leakage
Safety breaker
220-240V
circuit breaker
If the length of a connection wire is
10m or more, use φ2.0mm wire.
L
N
Use the specified wires and
connect them securely.
12