6. TROUBLESHOOTING

6-1 COMPRESSOR AND ELECTRIC COMPONENTS

1
Power Source.
Check the
2
resistance of
Motor
Compressor.
Check the
3
resistance of
PTC-Starter.
Check OLP .
4
Check
5
starting state.
Remove the PTC-Starter
from the Compressor
and measure the voltage
between T erminal C of
Compressor and
T erminals 5 or 6 of PTC.
No Voltage.
Applied voltage isn't
in the range of Rating
Voltage –10%.
Check the resistance
among M-C, S-C and
M-S in Motor
NO
Compressor.
Check the resistance
of two terminals in
PTC-Starter.
YES
Check if applying
a regular OLP .
Measure minimum
starting voltage after 5
min. for balancing cycle
pressure and cooling
the PTC.
(Rating Voltage
–10%)?
YES
OLP disconnected?
Advise the customer
to use a regular
Trans.
YES
Replace Compressor.
YES
NO
OLP works within
30 sec. in forcible
NO
OLP operation by
turning instant power
on and off.
NO
YES
Components start at
voltage –10% of
rated voltage.
- 13 -
YES
Replace OLP .
Check connection
condition.
Reconnect.
3
4
Replace
PTC-Starter.
YES
Replace OLP .
O.K.
NO
2
5
5
3
5
4
5
5
1