Single packaged gas/electric air cooled air conditioners (28 pages)
Summary of Contents for Unitary products group CPH 060
Page 1
Model CPH Horizontal Water-Cooled Air Conditioning Unit Supersedes: 145.14-IOM1 (708) Form 145.14-IOM1 (908) MODEL CPH 060, 096, 120 HORIZONTAL WATER-COOLED AIR CONDITIONING UNITS INSTALLATION & OPERATION INSTRUCTIONS...
FORM 145.14-IOM1 (908) IMPORTANT! READ BEFORE PROCEEDING! GENERAL SAFETY GUIDELINES This equipment is a relatively complicated apparatus. which it is situated, as well as severe personal injury or During installation, operation, maintenance or service, death to themselves and people at the site. individuals may be exposed to certain components or conditions including, but not limited to: refrigerants, oils, This document is intended for use by owner-authorized...
FORM 145.14-IOM1 (908) CHANGEABILITY OF THIS DOCUMENT In complying with Johnson Controls policy for continu- It is the responsibility of operating/service personnel as ous product improvement, the information contained to the applicability of these documents to the equipment in this document is subject to change without notice. in question.
FORM 145.14-IOM1 (908) TABLE OF CONTENTS TABLE OF CONTENTS General Information Installation Inspection of Equipment Site Selection General Data Dimensional Data Water Piping Water Pressure Drop Supply/Return Air Ductwork Electrical Wiring Fan Performance Data Motor and Drive Data RPM Adjustment Start-Up &...
FORM 145.14-IOM1 (908) GENERAL INFORMATION Installation time is minimized with all models. When plan- ning an installation consider power supply, thermostat, Our units are designed to accommodate the ever- condensate drain line, duct run, and service clearances. changing installation requirements of today’s market. A remote thermostat device is field supplied and installed All models 5 - 10 tons are shipped as factory-charged to control the unit operation.
Page 7
FORM 145.14-IOM1 (908) TYPICAL INSTALLATION LAYOUT (CPH060 SHOWN) LD13464 JOHNSON CONTROLS...
FORM 145.14-IOM1 (908) PRE-INSTALLATION INSPECTION OF EQUIPMENT UNIT MOUNTING All units are factory tested to ensure safe operation The 5 through 10 ton models are shipped as a fully and quality assembly. Units are packaged and sealed assembled integral package. Units are not intended for on shipping skids and shipped in first class condition.
FORM 145.14-IOM1 (908) WATER PIPING If the unit is running on mains water, we recommend adjusting the water regulating valve to give 100ºF leav- All factory installed water piping terminates inside the ing water temperature or 220 PSIG condensing tem- unit.
Page 13
FORM 145.14-IOM1 (908) WATERSIDE PRESSURE DROP (STANDARD UNIT-MANIFOLDED CONDENSERS) UNIT FLOW RATE (GPM) JOHNSON CONTROLS...
FORM 145.14-IOM1 (908) DUCTWORK All wiring must comply with applicable local and national codes (NEC). Type and location of disconnect switches must When installing ductwork, adhere to local Codes and comply with all applicable codes. sensible practice. Minimize duct runs and avoid abrupt changes in direction where possible.
Page 15
FORM 145.14-IOM1 (908) STANDARD EVAPORATOR MOTORS MODEL VOLTAGE COMPRESSOR EVAPORATOR MIN. CCT. MAX FUSE / AMPACITY CCT. BKR. AMP 060A 208-230/3/60 19.3 123.0 1.00 1800 27.23 460/3/60 49.5 1.00 1800 10.98 575/3/60 40.0 1.00 1800 9.30 096A 208-230/3/60 13.9 88.0 1.50 1800 35.68...
FORM 145.14-IOM1 (908) MOTOR AND PULLEY DATA STANDARD BLOWER MOTOR AND DRIVE DATA Drive Range Adjustable Fixed Model Motor Belts (RPM) Motor Pulley Blower Pulley Frame Eff. Pitch Dia. Pitch Dia. Designation Size (in) (in) 946-1419 1800 82.5 1.9-2.9 4L-400 968-1340 1-1/2 1800...
FORM 145.14-IOM1 (908) START-UP AND OPERATION There is no negative impact on durability caused by operating three phase Scroll compressors in the re- versed direction for a short period of time (under one Prior to starting unit for the first time, hour).
FORM 145.14-IOM1 (908) MAINTENANCE / SERVICE BLOWERS - Inspect both the evaporator and condenser blowers at DISCONNECT AND LOCK OUT POWER each regular service interval. Clean blower wheels as WHEN SERVICING UNIT. FAILURE TO needed. Bearings are permanently sealed ball type, and DO SO MAY RESULT IN PERSONAL IN- do not require lubrication.
Page 20
FORM 145.14-IOM1 (908) NOTES JOHNSON CONTROLS...
Page 21
FORM 145.14-IOM1 (908) NOTES JOHNSON CONTROLS...
Page 22
FORM 145.14-IOM1 (908) NOTES JOHNSON CONTROLS...
FORM 145.14-IOM1 (908) LIMITED WARRANTY Johnson Controls warrants this product to be free from defects in workmanship or material for a period of one year from date of original installation or 18 months from date of shipment, whichever comes first Johnson Controls obligation under this Warranty is LIMITED to repairing or replacing at our sole option, at our factory, any part thereof which shall be returned to our factory, transportation charges prepaid and which on examination proves to have been thus defective under normal domestic use not exceeding the fuel rating.