As soon as a unit is received, it should be inspected for possi- ble damage during transit. If damage is evident, the extent of the damage should be noted on the carrier's freight bill. A separate request for inspection by the carrier's agent should be made in writing. Unitary Products Group...
Utilization Range “A” in accordance with ARI Standard 110. TABLE 4: UNIT TEMPERATURE LIMITATIONS 5 Ton unit only. Temperature Minimum Maximum Wet Bulb Temperature (°F) of Air on Evaporator Coil Dry Bulb Temperature (°F) of Air on Heating Coil Unitary Products Group...
Figure 1, and make sure that its weight in the unit frame to accommodate hanger rods. Knockouts will be distributed equally. must be removed from the unit panels to expose these weld FIGURE 1 - SUSPENSION MOUNTING (HORIZONTAL) - KBU060, KBC090 AND 120 Unitary Products Group...
VERTICAL AND HORIZONTAL INSTALLATION - (a), the blower module can be repositioned in the field as KBU060, KBC090 AND 120 shown in illustrations (b) and (c) for maximum flexibility. These units are built in a single cabinet with two condensate •...
The supply air plenum and the return air grill should be used these sizes. Refer to Form 131002 for installation instructions in lieu of ductwork only when a free blow/free return applica- on the electric heater. tion is practical. Unitary Products Group...
Fiberglass insulation and a sealing material such as perma- NOTE: These units can only be piped from one side of the gum should be packed around refrigerant lines where they unit. Unitary Products Group...
WIRE IN ACCORDANCE WITH LOCAL terminals R and Y on 4TB can be AND NATIONAL ELECTRICAL CODES routed directly from the condensing unit to the thermostat if desired. FIGURE 11 - TYPICAL FIELD WIRING DIAGRAM KBU060, KBC090 AND 120 Unitary Products Group...
POWER WIRING volt power supply. Remove the knockout from the units rear panel (7/8" for KBU060 and KBC180, 1-3/8" for KBC090, and 120) for power CONTROL WIRE SIZING wiring conduit through this opening. Connect the conduit to Maximum Total Circuit...
NOTE: The tubes must be inserted and held in a position perpendicular to the airflow so that velocity pressure NOTE: Shut down the refrigeration system before taking will not affect the static pressure readings. any test measurements to assure a dry evaporator coil. Unitary Products Group...
292427-BIM-A-0307 TABLE 10: KBU060 (5 TON) BELT DRIVE BLOWER PERFORMANCE 5 TON BLOWER PERFORMANCE TURNS OPEN 0 Turns Open 1 Turn Open 2 Turns Open 3 Turns Open 4 Turns Open 5 Turns Open BHP CFM RPM W CFM RPM...
Certified dimensions will be provided upon request. GROMMET FIGURE 16 - UNIT DIMENSIONS KBU060 ACCESSORIES Overall dimensions of the unit will vary if an electric • ELECTRIC HEATER - Add 13” to unit height when used.
Allow enough clearance to trap the condensate drain Side with RETURN AIR opening 24” line. 24” Side with SUPPLY AIR opening 52” Side with PIPING CONNECTIONS Side opposite with PIPING CONNECTIONS 12” Side with access for both POWER & CONTROL WIRING Bottom Unitary Products Group...
Side Air with RETURN AIR opening 24” Allow enough clearance to trap the condensate drain lines. 24” Side with SUPPLY AIR opening 61” Side with PIPING CONNECTIONS 26” Side opposite PIPING CONNECTIONS Bottom Unitary Products Group...
Maintain belt tension to extend belt life. Replace when signs of failure begin to appear. Refer to the unit dimension detail (Figure 16) for the location of the filter access panel. Unitary Products Group...