• The height of the foundation must at least be 5-7/8 in. (150 mm )
from the floor.
In heavy snowfall areas, this height should be increased, depending
on the installation place and condition.
• The unit must be installed on a solid longitudinal foundation (steel
beam frame or concrete) and make sure the base under the unit is
larger than the gray marked area.
Dimensions for above figure
1 Hole for foundation bolt f9/16 in. (15 mm) dia: 4 positions
2 Inner dimension of
2
24-7/8 in. (631 mm)
the base
Distance between
3
29 in. (729 mm)
foundation bolt holes
4 Depth of unit
30-1/8 in. (765 mm)
Outer dimension of the
≥30-1/8 in. (765 mm)
5
base
Longitudinal foundation
72T type:
6
dimension
96-168T type:
Distance between
72T type:
7
foundation bolt holes
96-168T type:
• Fasten the unit in place using 4 foundation bolts
M12. It is best to screw in the foundation bolts
until their length remains 13/16 in. (20 mm)
above the foundation surface.
NOTE
• There are restrictions on the refrigerant pipe connecting order
between outdoor unit in the case of the multi system.
See 1.2.2. Outdoor unit combinations on page 2 for detail.
• When installing on a roof, make sure the roof floor is strong enough
and be sure to waterproof all work.
• Make sure the area around the machine drains properly by setting
up drainage grooves around the foundation.
• Drain water is sometimes discharged from the outdoor unit when it
is running.
• For anti-corrosion type, use nuts with resin washers. If the paint on
nut connections comes off, the anti-corrosion effect may decrease.
Resin washer
3P362438-1B English
1
6
7
36-9/6 in. (930 mm)
48-13/16 in. (1240 mm)
30-3/16 in. (766 mm)
42-3/8 in. (1076 mm)
A=13/16 in. (20 mm)

6 .5 . Method for removing shipping plate

The shipping plate installed over the compressor leg for protecting the
unit during transport must be removed. Proceed as shown in the figure
and procedure below.
Shipping plate
Front
144, 168 type
Front
96, 120 type
Front
72 type
1 Remove shipping plates.
2 Be sure to tighten compressor fixing bolts again. (9.1ft⋅lbf
(12.3 N⋅m))
Bolt
Shipping plate
NOTE
If the unit is operated with the shipping plate still attached, abnormal
vibration or noise may be generated.
Shipping plate
Shipping plate
Shipping plate
Compressor